5
-6
E1-03
V/f
pattern
selection
0
to E: Select from 15 preset patterns.
F:
Custom
user-set patterns
(Applicable
for setting E1-04
to
E1-10).
0
to F
F
No
Q
Q
No
302H
V/F
Selec-
tion
E1-04
Max.
output
frequency
(FMAX)
40.0
to
400.0
*4
60.0
Hz
*5
No
Q
Q
Q
303H
Max
Frequency
E1-05
Max.
voltage
(VMAX)
0.0
to
255.0
*3
200.0
V
*3*5
No
Q
Q
Q
304H
Max
Voltage
E1-06
Base
fre-
quency
(FA)
0.0
to
400.0
60.0
Hz
*5
No
Q
Q
Q
305H
Base
Fre-
quency
E1-09
Min.
output
frequency
(FMIN)
0.0
to
400.0
1.5
Hz
*5
No
Q
Q
Q
308H
Min
Fre-
quency
E1-13
Base
voltage
(VBASE)
Change
this setting only when making
advanced
adjustments for V/f in the
fixed
outputs area. Normally, there is
no
need to make these settings.
0.0
to
255.0
*3
0.0
V
*6
No
A
A
Q
30CH
Base
Voltage
E2-01
Motor
rated
current
Set
the motor rated current in amps.
This
set value becomes the base value
for
motor protection, torque limit, and
torque
control. It is set automatically
when
using autotuning.
0.32
to
6.40
*8
1.90
A
*7
No
Q
Q
Q
30EH
Motor
Rated
FLA
E2-04
Number
of
motor
poles Set the number of motor poles. The
value
is set automatically during auto-
tuning.
2
to 48
4
No
No
Q
No
311H
Number
of
Poles
F1-01
PG
constant
Set
the number of pulses per rotation
for
the PG (pulse generator or
encoder)
being used. (Do not set as a
multiple.)
0
to
60000
600
(1024)
*9
No
No
Q
No
380H
PG
Pulses/
Rev
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Regis-
ter
LCD
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Output voltage (V)
Frequency
(Hz)
VMAX
(E1-05)
VMIN
(E1-10)
FMIN
(E1-09)
FA
(E1-06)
FMAX
(E1-04)
VBASE
(E1-13)