Digital Operator Display Functions and Levels
5-
5
C1-01
Accelera-
tion
time 1
Set
the acceleration time in seconds
for
the output frequency to climb from
0%
to 100%.
0.0
to
6000.0
*1
10.0
s
Yes
Q
Q
Q
200H
Accel
Time
1
C1-02
Decelera-
tion
time 1
Set
the deceleration time in seconds
for
the output frequency to fall from
100%
to 0%.
Yes
Q
Q
Q
201H
Decel
Time
1
C6-01
CT/VT
selection
0:
CT (low carrier, constant torque,
150%
per minute)
1: VT
(high carrier, variable torque,
120%
per minute)
0
or 1
1
No
Q
Q
Q
223H
Heavy/Nor-
mal
Duty
C6-02
Carrier
fre-
quency
selection
Select
carrier wave fixed pattern.
Select
F to enable detailed settings
using
parameters C6-03 to C6-07.
0
to F
6
*2
No
Q
Q
Q
224H
CarrierFreq
Sel
d1-01
Frequency
reference
1
Set
the frequency reference in the unit
specified
in o1-03 (Frequency Units
for
Reference Setting And Monitor,
default:
Hz)
0
to
400.00
0.00
Hz
Yes
Q
Q
Q
280H
Reference
1
d1-02
Frequency
reference
2 Frequency reference when multi-step
speed
command 1 is ON for a multi-
function
input (unit: Set in o1-03).
0.00
Hz
Yes
Q
Q
Q
281H
Reference
2
d1-03
Frequency
reference
3 Frequency reference when multi-step
speed
command 2 is ON for a multi-
function
input (unit: Set in o1-03).
0.00
Hz
Yes
Q
Q
Q
282H
Reference
3
d1-04
Frequency
reference
4
Frequency
reference when multi-step
speed
command 1 and 2 are ON for a
multi-function
input (unit: Set in o1-
03).
0.00
Hz
Yes
Q
Q
Q
283H
Reference
4
d1-17
Jog
frequency
reference
Frequency
reference when Jog Fre-
quency
Selection, FJOG command, or
RJOG
command is ON for a multi-
function
input (unit: Set in o1-03).
6.00
Hz
Yes
Q
Q
Q
292H
Jog
Reference
E1-01
Input
volt-
age
setting
Set
the Inverter input voltage in 1 volt.
This
set value will be the basis for the
protection
functions.
155
to
255
*3
200
V
*3
No
Q
Q
Q
300H
Input
Volt-
age
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
Regis-
ter
LCD
Display
V/f
V/f
with
PG
Open
Loop
Vec-
tor
Summary of Contents for SYSDRIVE 3G3RV
Page 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Page 36: ...1 22...
Page 106: ...3 14...
Page 126: ...4 20...
Page 216: ...5 90...
Page 388: ...7 26...