6
-128
n
Manual
Motor
Constant
Parameter
Setting
Methods
The
motor constant parameters settings methods are given below. Make (enter) settings referring to the motor
test
report.
Motor
Rated
Current
Setting
Set
E2-01 to the rated current on the motor nameplate.
Motor
Rated
Slip
Setting
Set
E2-02 to the motor rated slip calculated from the number of rated rotations on the motor nameplate.
Amount
of motor rated slip = Motor rated frequency (Hz) - No. of rated rotations (r/min) x No. of motor poles/
120.
Motor
No-Load
Current
Setting
Set
E2-03 to the motor no-load current using the rated voltage and rated frequency. The motor no-load current
is
not normally written on the motor nameplate. Consult the motor manufacturer.
Factory
setting is the no-load current value for a standard Yaskawa 4-pole motor.
Number
of
Motor
Poles
Setting
E2-04
is displayed only when V/f control method with PG is selected. Set the number of motor poles (number
of
poles) as written on the motor nameplate.
Motor
Line-to-Line
Resistance
Setting
E2-05
is set automatically when performing motor line-to-line resistance autotuning. When you cannot per-
form
tuning, consult the motor manufacturer for the line-to-line resistance value. Calculate the resistance from
the
line-to-line resistance value in the motor test report using the following formula, and then make the setting
accordingly.
•
E-type
isolation: [Line-to line resistance (
Ω
)
at 75
°
C
of test report]
×
0.92 (
Ω
)
•
B-type
isolation: [Line-to line resistance (
Ω
)
at 75
°
C
of test repor]t
×
0.92 (
Ω
)
•
F-type
isolation: [Line-to line resistance (
Ω
)
at 115
°
C
of test report]
×
0.87 (
Ω
)
Motor
Leak
Inductance
Setting
Set
the amount of voltage drop due to motor leak inductance in E2-06 using the percentage over the motor
rated
voltage. Make this setting when the high-speed motor inductance is small. If the inductance is not writ-
ten
on the motor nameplate, consult the motor manufacturer.
Motor
Iron
Saturation
Coefficients
1
and
2
Settings
E2-07
and E2-08 are set automatically using autotuning.
Motor
Iron
Loss
for
Torque
Compensation
Setting
E2-10
is displayed only when in V/f control method. To increase the torque compensation accuracy when in
V/f
control method, set the motor iron loss in Watts.