IMPORTANT
1. Control circuit terminals are arranged as shown below.
2. The output current capacity of the +V terminal is 20 mA.
3. Disable the stall prevention during deceleration (set parameter L3-04 to 0) when using a Braking Resistor
Unit. If this parameter is not changed to disable stall prevention, the system may not stop during decelera-
tion.
4. Main circuit terminals are indicated with double circles and control circuit terminals are indicated with single
circles.
5. Sequence input signals S1 to S7 are labeled for sequence connections (0 V common and sinking mode)
for no-voltage contacts or NPN transistors. These are the default settings.
For PNP transistor sequence connections (+24-V common and sourcing mode) or to provide a 24-V exter-
nal power supply, refer toTable
2.18.
6. The master speed frequency reference can set to input either a voltage (terminal A1) or current (terminal
A2) by changing the setting of parameter H3-13. The default setting is for a voltage reference input.
7. The multi-function analog output is a dedicated meter output for an analog frequency meter, ammeter, volt-
meter, wattmeter, etc. Do not use this output for feedback control or for any other control purpose.
8. DC reactors to improve the input power factor built into 200-V class Inverters for 22 to 110 kW and 400-V
class Inverters for 22 to 160 kW. A DC reactor is thus an option only for Inverters for 18.5 kW or less.
Remove the short bar when connecting a DC reactor to Inverters for 18.5 kW or less.
9. Set parameter L8-01 to 1 when using a Braking Resistor (3G3IV-PERF). When using a Braking Resistor
Unit, a cutoff sequence for the power supply must be made using a thermal relay trip.