Wiring Control Circuit Terminals for European Models
2-
41
K
K
K
K
Control
Circuit
Terminal
Functions
The
functions of the control circuit terminals are shown in Table 2.21. Use the appropriate terminals for the
correct
purposes.
Table 2.21 Control Circuit Terminals
Type
No.
Signal
Name
Function
Signal
Level
Se-
quence
input
signals
S1
Forward
run/stop command
Forward
run when ON; stopped when OFF.
24
VDC, 8 mA
Photocoupler
isolation
S2
Reverse
run/stop command
Reverse
run when ON; stopped when OFF.
S3
External
fault input
*1
Fault
when ON.
Functions
are
selected
by set-
ting
H1-01 to
H1-05.
S4
Fault
reset
*
Reset
when ON
S5
Multi-step
speed reference
1
*1
(Master/auxiliary
switch)
Auxiliary
frequency ref-
erence
when ON.
S6
Multi-step
speed reference
2
*1
Multi-step
setting 2 when
ON.
S7
Jog
frequency reference
*1
Jog
frequency when ON.
SC
Sequence
input common
-
-
SP
+24
V power for S1 to S7
SN
-24
V power for S1 to S7
Analog
input
signals
+V
15
V power output
15
V power supply for analog references
15
V
(Max.
current: 20 mA)
-V
-15
V power output
-15
V power supply for analog references
-15
V
(Max.
current: 20 mA)
A1
Frequency
reference
0
to +10 V/100% (when H3-01 = 0)
-10
to +10 V/-100% to +100% (when H3-01
=
1)
*4
0
to +10 V(20 k
Ω
)
A2
Multi-function
analog input
4
to 20 mA/100%
0
to +10 V/100%
Function
is
selected
by set-
ting
H3-09.
4
to 20 mA(250
Ω
)
0
to +10 V(20k
Ω
)
AC
Analog
reference common
-
-
E(G)
Shield
wire, optional ground
line
connection point
-
-
Se-
quence
output
signals
M1
Running
signal
(1NO
contact)
Operating
when ON.
Multi-function
contact
outputs
Dry
contacts
Contact
capacity:
1
A max. at 250 VAC
1
A max. at 30 VDC
M2
M3
Zero
speed
Zero
level (b2-01) or
below
when ON
Multi-function
contact
outputs
Dry
contacts
Contact
capacity:
1
A max. at 250 VAC
1
A max. at 30 VDC
M4
M5
Frequency
agree 1
Within
±
2
Hz of set fre-
quency
when ON
M6
MA
Fault
output signal (SPDT)
Fault
when CLOSED across MA and MC
Fault
when OPEN across MB and MC
Dry
contacts
Contact
capacity:
1
A max. at 250 VAC
1
A max. at 30 VDC
MB
MC
Summary of Contents for SYSDRIVE 3G3RV
Page 1: ...USER S MANUAL SYSDRIVE 3G3RV High function General purpose Inverters Cat No I532 E1 1...
Page 36: ...1 22...
Page 106: ...3 14...
Page 126: ...4 20...
Page 216: ...5 90...