Individual Functions
6-
125
K
K
K
K
Energy-saving
To
perform energy saving, set b8-01 (Energy Saving Mode Selection) to 1. Energy-saving control can be per-
formed
using both V/f control and open loop vector control. The parameters to be adjusted are different for
each.
In V/f control, adjust b8-04 to b8-06, and in open loop vector, adjust b8-02 and b8-03.
n
Related
Parameters
* 1. The
factory setting is 1.0 when using V/f control with PG.
* 2. The
factory setting is 2.00 s for an Inverter capacity of 55 kW and over.
* 3. The
same capacity as the Inverter will be set by initializing the parameters.
* 4. The
factory settings depend on the Inverter capacity.
* 5. The
factory settings depend on the Inverter capacity. (The values shown are for 200-V class, 0.4 kW Inverters.)
Param-
eter
Num-
ber
Name
Details
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
LCD
Display
b8-01
Energy-saving
mode
selection
Select
whether to enable or disable energy-saving con-
trol.
0:
Disable
1:
Enable
0
or 1
0
No
A
A
A
Energy
Save
Sel
b8-02
Energy-saving
gain
Set
the energy-saving gain with the open loop vector
control
method.
0.0
to
10.0
0.7
*1
Yes
No
No
A
Energy
Save
Gain
b8-03
Energy-saving
filter
time con-
stant
Set
the energy-saving filter time constant with the open
loop
vector control method.
0.00
to
10.0
0.50
s
*2
Yes
No
No
A
Energy
Save
F.T
b8-04
Energy-saving
coefficient
Set
the maximum motor efficiency value.
Set
the motor rated capacity in E2-11, and adjust the
value
by 5% at a time until output power reaches a mini-
mum
value.
0.0
to
655.00
*3
*4
No
A
A
No
Energy
Save
COEF
b8-05
Power
detec-
tion
filter time
constant
Set
the time constant for output power detection.
0
to 2000
20
ms
No
A
A
No
kW
Filter Time
b8-06
Search
opera-
tion
voltage
limiter
Set
the limit value of the voltage control range during
search
operation.
Perform
search operation to optimize operations using
minute
variations in voltage using energy-saving con-
trol.
Set to 0 to disable the search operation. 100% is the
motor
base voltage.
0
to 100
0%
No
A
A
No
Search
V Limit
E2-02
Motor
rated slip
Sets
the motor rated slip in hertz. These set values will
become
the reference values for slip compensation. This
parameter
is automatically set during autotuning.
0.00
to
20.00
2.90
Hz
*5
No
A
A
A
Motor
Rated
Slip
E2-11
Motor
rated
output
Set
the rated output of the motor in units of 0.01 kW.
This
parameter is automatically set during autotuning.
0.00
to
650.00
0.40
*5
No
Q
Q
Q
Mtr
Rated
Power