BEFORE USE ....

Thank you for choosing M-System.  Before use, check the
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.

■ 

PACKAGE INCLUDES:

Signal conditioner ....................................................... (1)

■ 

MODEL NO.

Check that model No. described on specification label is
exactly what you ordered.

■ 

INSTRUCTION MANUAL

This manual describes necessary points of caution when you
use this product, installation, connection and basic mainte-
nance procedures.
For changing I/O ranges, the JX Configurator Connection Kit
(model: JXCON) is required.  For detailed information, refer
to the data sheet and instruction manual for the JXCON.

POINTS OF CAUTION

■ 

M8XV3: CONFORMITY WITH EC DIRECTIVES

• Operational insulation is maintained between signal input
and output.
• The equipment must be mounted inside a panel.
• Install lightning surge protectors for those wires connected
to remote locations.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in a
panel system.  The user may have to review the CE require-
ments in regard to the whole system and employ additional
protective measures to ensure the CE conformity.

■ 

POWER INPUT RATING & OPERATIONAL RANGE

• Check the power rating for the unit on the specification
label.

Rating 24V DC: 24V 

±

10%, approx. 50mA

• Power fuse: A power fuse of the rating as shown below is
incorporated for safety.  However, DO NOT replace it by the
user.

T 0.25A 125V

■ 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration.  Do not apply physical impact to the unit.
• Environmental temperature must be within 0 to 55

°

C (32

to 131

°

F) with relative humidity within 30 to 95% RH in order

to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with
cables, etc.

■ 

WIRING

• Do not install cables (input and output) close to noise
sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present.  Do not install them in the same duct.

■ 

AND ....

• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.

COMPONENT IDENTIFICATION

INSTALLATION

Use Installation Base (model: M8BS

).

TERMINAL CONNECTIONS

Connect the unit referrint the drawings below.

■ 

EXTERNAL DIMENSIONS  mm (inch)

■ 

CONNECTION DIAGRAM

INSTRUCTION  MANUAL

MODEL

SIGNAL CONVERTER

(PC programmable)

Specification

Label

Mounting Screw

Body

+

Installation Base

OUTPUT 1

6

7

8

9

10

11

+

+

OUTPUT 2

1

2

A

B

POWER

+

INPUT

CONFIGURATOR

JACK

I/O PINS

17.5(.69)

48 (1.89)

75 (2.95)

83 (3.27)

M8XV2
M8XV3