M8XV2 / M8XV3
EM-5469 Rev.2
P. 1 / 3
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■
PACKAGE INCLUDES:
Signal conditioner ....................................................... (1)
■
MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■
INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic mainte-
nance procedures.
For changing I/O ranges, the JX Configurator Connection Kit
(model: JXCON) is required. For detailed information, refer
to the data sheet and instruction manual for the JXCON.
POINTS OF CAUTION
■
M8XV3: CONFORMITY WITH EC DIRECTIVES
• Operational insulation is maintained between signal input
and output.
• The equipment must be mounted inside a panel.
• Install lightning surge protectors for those wires connected
to remote locations.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in a
panel system. The user may have to review the CE require-
ments in regard to the whole system and employ additional
protective measures to ensure the CE conformity.
■
POWER INPUT RATING & OPERATIONAL RANGE
• Check the power rating for the unit on the specification
label.
Rating 24V DC: 24V
±
10%, approx. 50mA
• Power fuse: A power fuse of the rating as shown below is
incorporated for safety. However, DO NOT replace it by the
user.
T 0.25A 125V
■
ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within 0 to 55
°
C (32
to 131
°
F) with relative humidity within 30 to 95% RH in order
to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with
cables, etc.
■
WIRING
• Do not install cables (input and output) close to noise
sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■
AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
COMPONENT IDENTIFICATION
INSTALLATION
Use Installation Base (model: M8BS
❑
).
TERMINAL CONNECTIONS
Connect the unit referrint the drawings below.
■
EXTERNAL DIMENSIONS mm (inch)
■
CONNECTION DIAGRAM
INSTRUCTION MANUAL
MODEL
SIGNAL CONVERTER
(PC programmable)
Specification
Label
Mounting Screw
Body
+
–
Installation Base
OUTPUT 1
6
7
8
9
10
11
+
–
+
–
OUTPUT 2
1
2
A
B
POWER
+
–
INPUT
CONFIGURATOR
JACK
I/O PINS
17.5(.69)
48 (1.89)
75 (2.95)
83 (3.27)
M8XV2
M8XV3