L6-01
Torque
detection selection
1
0:
Overtorque/undertorque detection disabled.
1:
Overtorque detection only with speed agree-
ment;
operation continues after overtorque
(warning).
2:
Overtorque detected continuously during oper-
ation;
operation continues after overtorque
(warning).
3:
Overtorque detection only with speed agree-
ment;
output stopped upon detection (pro-
tected
operation).
4:
Overtorque detected continuously during oper-
ation;
output stopped upon detection (pro-
tected
operation).
5:
Undertorque detection only with speed agree-
ment;
operation continues after overtorque
(warning).
6:
Undertorque detected continuously during
operation;
operation continues after over-
torque
(warning).
7:
Undertorque detection only with speed agree-
ment;
output stopped upon detection (pro-
tected
operation).
8:
Undertorque detected continuously during
operation;
output stopped upon detection (pro-
tected
operation).
0
to 8
0
No
A
A
A
Torq
Det 1 Sel
L6-02
Torque
detection level 1
Open-loop
vector control: Motor rated torque is
set
as 100%.
V/f
control: Inverter rated current is set as 100%.
0
to 300
150%
No
A
A
A
Torq
Det 1 Lvl
L6-03
Torque
detection time 1
Set
the overtorque/undertorque detection time in
1-second
units.
0.0
to
10.0
0.1
s
No
A
A
A
Torq
Det 1 Time
L6-04
Torque
detection selection
2
Output
of torque detection 1 is enabled by setting
17
for H2-
oo
and output of torque detection 1 is
enabled
by setting 18 or 18 for H2-
oo
.
0
to 8
0
No
A
A
A
Torq
Det 2 Sel
L6-05
Torque
detection level 2
0
to
300
150%
No
A
A
A
Torq
Det 2 Lvl
L6-06
Torque
detection time 2
0.0
to
10.0
0.1
s
No
A
A
A
Torq
Det 2 Time
Set
Value
Function
Control
Methods
V/f
V/f
with
PG
Open
Loop
Vec-
tor
B
Overtorque/undertorque
detection 1 NO
(NO
contact: Overtorque detection and undertorque detection enabled when contact is ON)
Yes
Yes
Yes
17
Overtorque/undertorque
detection 1 NC
(NC
contact: Overtorque detection and undertorque detection enabled when contact is OFF)
Yes
Yes
Yes
18
Overtorque/undertorque
detection 2 NO
(NO
contact: Overtorque detection and undertorque detection enabled when contact is ON)
Yes
Yes
Yes
19
Overtorque/undertorque
detection 2 NC
(NC
contact: Overtorque detection and undertorque detection enabled when contact is OFF)