7. SPECIAL ADJUSTMENT FUNCTIONS
7 - 28
(2) Instantaneous power failure time of the control circuit power supply < [Pr. PF25 SEMI-F47 function -
Instantaneous power failure detection time]
Operation status differs depending on how bus voltage decrease.
(a) When the bus voltage decrease lower than Undervoltage level within the instantaneous power failure
time of the control circuit power supply
[AL. 10 Undervoltage] occurs when the bus voltage decrease lower than Undervoltage level
regardless of the enabled instantaneous power failure tough drive.
[Pr. PF25]
Instantaneous power failure time of the control circuit power supply
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Control circuit
power supply
Bus voltage
Undervoltage level
(Note)
ALM
(Malfunction)
MTTR
(During tough drive)
MBR
(Electromagnetic
brake interlock)
Base circuit
WNG
(Warning)
ON (energization)
OFF (power failure)
Note. Refer to table 7.1 for the undervoltage level.
Summary of Contents for MR-J4-100B(-RJ)
Page 17: ...8 MEMO ...
Page 143: ...4 STARTUP 4 20 MEMO ...
Page 199: ...5 PARAMETERS 5 56 MEMO ...
Page 227: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Page 281: ...8 TROUBLESHOOTING 8 16 MEMO ...
Page 303: ...9 DIMENSIONS 9 22 MEMO ...
Page 319: ...10 CHARACTERISTICS 10 16 MEMO ...
Page 429: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 110 MEMO ...
Page 435: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 6 MEMO ...
Page 483: ...14 USING A LINEAR SERVO MOTOR 14 34 MEMO ...
Page 531: ...16 FULLY CLOSED LOOP SYSTEM 16 26 MEMO ...
Page 613: ...17 APPLICATION OF FUNCTIONS 17 82 MEMO ...
Page 654: ...APPENDIX App 41 ...