5. PARAMETERS
5 - 21
No.
Symbol
Name and function
Initial
value
[unit]
Setting
range
PA25 OTHOV One-touch tuning - Overshoot permissible level
This is used to set a permissible value of overshoot amount with a percentage to in-position
range.
However, setting "0" will be 50%.
0
[%]
0 to 100
PA26
*AOP5 Function selection A-5
Refer to the
"Name and
function" column.
Setting
digit
Explanation
Initial
value
_ _ _ x
Torque limit function selection at instantaneous power failure
(instantaneous power failure tough drive selection)
0: Disabled
1: Enabled
When an instantaneous power failure occurs during operation, you
can save electric energy charged in the capacitor in the servo
amplifier by limiting torque at acceleration. You can also delay the
time until [AL. 10.2 Voltage drop in the main circuit power] occurs
with instantaneous power failure tough drive function. Doing this will
enable you to set a longer time in [Pr. PF25 SEMI-F47 function -
Instantaneous power failure detection time].
To enable the torque limit function at instantaneous power failure,
select "Enabled (_ 1 _ _)" of "SEMI-F47 function selection" in [Pr.
PA20].
This parameter setting is used with servo amplifier with software
version A6 or later.
0h
_ _ x _
For manufacturer setting
0h
_ x _ _
0h
x _ _ _
0h
Summary of Contents for MR-J4-100B(-RJ)
Page 17: ...8 MEMO ...
Page 143: ...4 STARTUP 4 20 MEMO ...
Page 199: ...5 PARAMETERS 5 56 MEMO ...
Page 227: ...6 NORMAL GAIN ADJUSTMENT 6 28 MEMO ...
Page 281: ...8 TROUBLESHOOTING 8 16 MEMO ...
Page 303: ...9 DIMENSIONS 9 22 MEMO ...
Page 319: ...10 CHARACTERISTICS 10 16 MEMO ...
Page 429: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 110 MEMO ...
Page 435: ...12 ABSOLUTE POSITION DETECTION SYSTEM 12 6 MEMO ...
Page 483: ...14 USING A LINEAR SERVO MOTOR 14 34 MEMO ...
Page 531: ...16 FULLY CLOSED LOOP SYSTEM 16 26 MEMO ...
Page 613: ...17 APPLICATION OF FUNCTIONS 17 82 MEMO ...
Page 654: ...APPENDIX App 41 ...