![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 176](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886176.webp)
Parameter List
Parameters
5 - 4
Sec
o
nd func
tio
ns
44
F020
Second acceleration/deceleration time
0 to 3600 s
0.1 s
5 s
45
F021
Second deceleration time
0 to 3600 s, 9999
0.1 s
9999
46
G010
Second torque boost
0 to 30%, 9999
0.1%
9999
47
G011
Second V/F (base frequency)
0 to 590 Hz, 9999
0.01 Hz
9999
48
H600
Second stall prevention operation level
0 to 400%
0.1%
120%
110%
49
H601
Second stall prevention operation
frequency
0 to 590 Hz, 9999
0.01 Hz
0 Hz
50
M444
Second output frequency detection
0 to 590 Hz
0.01 Hz
30 Hz
51
H010
C203
Second electronic thermal O/L relay
Rated second motor current
0.01 A
9999
0 to 3600 A, 9999
0.1 A
M
o
ni
to
r func
tions
52
M100
Operation panel main monitor
selection
0, 5 to 14, 17, 18, 20,
23 to 25, 34, 38, 40 to 45,
50 to 57, 61, 62, 64, 67 to
69, 81 to 96, 98, 100
1
0
54
M300
FM/CA terminal function selection
1 to 3, 5 to 14, 17, 18, 21,
24, 34, 50, 52, 53, 61, 62,
67, 69, 70, 85, 87 to 90,
92, 93, 95, 98
1
1
55
M040
Frequency monitoring reference
0 to 590 Hz
0.01 Hz
60 Hz
50 Hz
56
M041
Current monitoring reference
0.01 A
Inverter rated
current
0 to 3600 A
0.1 A
Au
to
m
a
ti
c
re
st
a
rt
57
A702
Restart coasting time
0, 0.1 to 30 s, 9999
0.1 s
9999
58
A703
Restart cushion time
0 to 60 s
0.1 s
1 s
⎯
59
F101
Remote function selection
0 to 3, 11 to 13
1
0
⎯
60
G030
Energy saving control selection
0, 4, 9
1
0
⎯
65
H300
Retry selection
0 to 5
1
0
⎯
66
H611
Stall prevention operation reduction
starting frequency
0 to 590 Hz
0.01 Hz
60 Hz
50 Hz
Retr
y
67
H301
Number of retries at fault occurrence
0 to 10, 101 to 110
1
0
68
H302
Retry waiting time
0.1 to 600 s
0.1 s
1 s
69
H303
Retry count display erase
0
1
0
⎯
70
G107
Parameter for manufacturer setting. Do not set.
⎯
71
C100
Applied motor
0 to 6, 13 to 16, 20, 23, 24,
40, 43, 44, 50, 53, 54, 70,
73, 74, 210, 213, 214,
240, 243, 244, 8090,
8093, 8094, 9090, 9093,
9094
1
0
5-41,
⎯
72
E600
PWM frequency selection
0 to 15
1
2
0 to 6, 25
⎯
73
T000
Analog input selection
0 to 7, 10 to 17
1
1
⎯
74
T002
Input filter time constant
0 to 8
1
1
Fu
n
c
ti
o
n
Pr.
Pr.
group
Name
Setting range
Minimum
setting
increments
Initial value
Refer
to page
Cu
st
o
m
e
r
setting
FM
CA
Tab. 5-2:
Parameter overview (by number) (3)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......