Parameters
(A) Application parameters
FR-F800
5 - 363
Input/output signals
●
Assigning the PID control valid terminal signal (X14) to the input terminal by Pr. 178 to Pr. 189
(input terminal function selection) enables PID control to be performed only when the X14 signal
is turned ON. When the X14 signal is OFF, regular inverter running is performed without PID action.
●
Input signal
●
Output signal
NOTES
The multistage set point input is not available for the second PID.
The priority of the set point input is as follows: Pr. 1460 to Pr. 1466 > Pr. 133 > Pr. 128.
Signal Function
Pr. 178 to
Pr. 189 setting
Description
X14
PID control valid terminal
14
When the signal is assigned to the input terminal, PID
control is enabled when the signal is ON.
X80
Second PID control valid terminal
80
PDI1
PID multistage set point setting 1
38
The set point set in Pr. 1460 to Pr. 1466 can be selected by
combining the ON/OFF status of the signals.
PDI2
PID multistage set point setting 2
39
PDI3
PID multistage set point setting 3
40
X64
During retry
64
PID control is switched between forward and reverse action
without changing parameters by turning ON the signal.
X79
Second PID forward/reverse action
switchover
79
X72
PID P control switchover
72
Integral and differential values can be reset by turning the
signal ON.
X73
Second PID P control switchover
73
Tab. 5-172:
Input signals and parameter settings
Signal Function
Pr. 190 to Pr. 196
setting value
Description
Positive
logic
Negative
logic
FUP
PID upper limit
15
115
Output when the measured value signal exceeds Pr. 131 "PID
upper limit" (Pr. 1143 "Second PID upper limit").
FUP2
Second PID upper limit
201
301
FDN
PID lower limit
14
114
Output when the measured value signal exceeds Pr. 132 "PID
lower limit" (Pr. 1144 "Second PID lower limit").
FDN2
Second PID lower limit
200
300
RL
PID forward/reverse
rotation output
16
116
"Hi" is output when the output display of the parameter unit is
forward rotation (FWD), and "Low" is output when the display is
reverse rotation (REV) and stop (STOP).
RL2
Second PID forward/
reverse rotation output
202
302
PID
During PID control
activated
47
147
Turns ON during PID control.
When the PID calculation result is not reflected to the output
frequency (Pr. 128 < "2000"), the PID signal turns OFF at turn OFF
of the start signal.
When the PID calculation result is reflected to the output
frequency (Pr. 128
≥
"2000"), the PID signal turns ON regardless of
the start signal status during PID calculation.
PID2
Second During PID
control activated
203
303
SLEEP
PID output interruption
70
170
Set Pr. 575 "Output interruption detection time" (Pr. 1147 "Second
output interruption detection time")
≠
"9999". This signal turns
ON when the PID output suspension function is activated.
SLEEP2
During second PID
output shutoff
204
304
Tab. 5-173:
Output signals and parameter settings
NOTE
Changing the terminal functions with Pr. 178 to Pr. 189 and Pr. 190 to Pr. 196 may affect other
functions. Set parameters after confirming the function of each terminal.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......