Protective functions
Causes and corrective actions
FR-F800
6 - 31
Operation panel
indication
E.EHR
FR-LU-08
Ethernet comm fault
Name
Ethernet communication fault (FR-F800-E only)
Description
Appears when Ethernet communication is interrupted by physical factors while Pr. 1431
"Ethernet signal loss detection function selection" = "3".
The inverter trips when Ethernet communication is cut off for the time set in Pr. 1432
"Ethernet communication check time interval" or longer between the inverter and all
devices with the IP addresses in the range specified for the Ethernet command source
selection (Pr. 1449 to Pr. 1454).
Stops the inverter output when excessive noise occurs around the inverter.
When the CC-Link IE Field Network Basic is used, the inverter output is shut off when the
data addressed to the own station is not received for the predetermined timeout period or
longer, or when the status bit of the cyclic transmission addressed to the own station turns
OFF (when the master controller gives a command to stop the cyclic transmission). (For the
details of the timeout period, status bit of the cyclic transmission, and command to stop the
cyclic transmission, refer to the Instruction Manual of the master controller which supports
the CC-Link IE Field Network Basic.)
Check point
Check that the Ethernet board is installed onto the connector securely.
Check for a break in the Ethernet cable.
Check that the Pr. 1432 setting is not too short.
Check for excessive noise around the inverter.
When the CC-Link IE Field Network Basic is used, check that the timeout period set in the
master is not shorter than the period during which the inverter does not receive the data
addressed to the own station.
When the CC-Link IE Field Network Basic is used, check that the status bit of the cyclic
transmission addressed to the own station is not OFF.
Corrective action
Connect the Ethernet board securely.
Check that the Ethernet cable is correctly connected to the Ethernet connector. Check that
the Ethernet cable is not broken.
Set a larger value in Pr.1432.
When excessive noise occurs around the inverter, change the communication setting of the
master. (The noise may be reduced by setting a shorter timeout period or increasing the
number of retries in the communication setting of the master.)
When the CC-Link IE Field Network Basic is used, set a timeout period longer than the period
during which the inverter does not receive the data addressed to the own station.
When the CC-Link IE Field Network Basic is used, turn ON the status bit of the cyclic
transmission addressed to the own station.
Operation panel
indication
E. 1 to E. 3
to
FR-LU08
Fault 1 to Fault 3
Name
Option fault
Description
The inverter trips when a contact fault is found between the inverter and the plug-in option, or
when the communication option is not connected to the connector 1.
Appears when the switch for manufacturer setting of the plug-in option is changed.
Check point
Check that the plug-in option is plugged into the connector properly.
(1 to 3 indicate connector numbers for connection of options.)
Check for excessive noise around the inverter.
Check if the communication option is connected to the connector 2 or 3.
Corrective action
Connect the plug-in option securely.
Take measures against noises if there are devices producing excess electrical noises around
the inverter.
If the situation does not improve after taking the above measure, please contact your sales
representative.
Connect the communication option to the connector 1.
Set the switch on the plug-in option, which is for manufacturer setting, back to the initial
setting. (Refer to the Instruction Manual of each option.)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......