(M) Monitor display and monitor output signal
Parameters
5 - 234
71
171
RO1
Commercial power
supply side motor 1
connection
Output depending on the motor drive
conditions when the multi-pump
function is used.
Pr. 575 to
Pr. 591
72
172
RO2
Commercial power
supply side motor 2
connection RO2
73
173
RO3
Commercial power
supply side motor 3
connection RO3
74
174
RO4
Commercial power
supply side motor 4
connection
75
175
RIO1
Inverter side motor 1
connection RIO1
76
176
RIO2
Inverter side motor 2
connection RIO2
77
177
RIO3
Inverter side motor 3
connection RIO3
78
178
RIO4
Inverter side motor 4
connection RIO4
79
179
Y79
Pulse train output of
output power
Output in pulses every time the
accumulated output power of the
inverter reaches the Pr. 799 setting.
Pr. 799
80
180
SAFE
Safety monitor output
(SAFE) signal
The SAFE signal is output when the safety
stop function is activated and the
internal safety circuit status is normal.
—
82
182
Y82
BACnet binary output
Enables output from the Binary Output
object for BACnet communication.
Pr. 549
85
185
Y85
DC current feeding
Output when there is a power failure or
undervoltage for the AC current.
Pr. 30
86
186
Y86
Control circuit capacitor
life
(for Pr. 313 to Pr. 322)
Output when the control circuit capacitor
approaches the end of its life.
Pr. 255 to
Pr. 259
87
187
Y87
Main circuit capacitor life
(for Pr. 313 to Pr. 322)
Output when the main circuit capacitor
approaches the end of its life.
88
188
Y88
Cooling fan life
(for Pr. 313 to Pr. 322)
Output when the cooling fan approaches
the end of its life.
89
189
Y89
Inrush current limit circuit
life
(for Pr. 313 to Pr. 322)
Output when the inrush current limit
circuit approaches the end of its life.
90
190
Y90
Life alarm
Output when any of the control circuit
capacitor, main circuit capacitor and
inrush current limit circuit or the cooling
fan approaches the end of its life.
91
191
Y91
Fault output 3(power-OFF
signal)
Output when an error occurs due to an
inverter circuit fault or connection fault.
⎯
92
192
Y92
Energy saving average
value updated timing
Switches between ON and OFF each time
the average power saving is updated
when using the power saving monitor.
This cannot be set in Pr. 195 or Pr. 196,Pr.
320 to Pr. 322 (relay output terminal).
Pr. 52, Pr. 54,
Pr. 158,
Pr. 891 to
Pr. 899
93
193
Y93
Current average monitor
signal
Outputs the average current and
maintenance timer value as a pulse.
This cannot be set in Pr. 195 or Pr. 196,
Pr. 320 to Pr. 322 (relay output terminal).
Pr. 555 to
Pr. 557
Setting
Signal
name
Function
Operation
Related
parameter
Refer to
page
Positive
logic
Negative
logic
Tab. 5-101:
Output terminal function assignment (3)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......