Parameters
(N) Operation via communication and its settings
FR-F800
5 - 529
Ethernet signal loss detection (Pr. 1431)
Use Pr. 1431 to set the operation when Ethernet communication is interrupted by physical factors in-
cluding disconnection of the Ethernet board or Ethernet cable or damages on the Ethernet cable.
Ethernet communication check time interval (Pr. 1432)
●
If a signal loss (communication stop) is detected between the inverter and all the devices with IP
addresses in the range for Ethernet command source selection (Pr. 1449 to Pr. 1454) as a result of
a signal loss detection, a communication error (E.EHR) occurs and the inverter trips.
●
When "9999 (initial value)" is set in Pr. 1432, the communication check (signal loss detection) will
not be performed.
●
The monitored items and parameter settings can be read via Ethernet when "0" is set in Pr. 1432,
but a communication error (E.EHR) occurs instantly when the operation mode is switched to the
Network operation.
●
A signal loss detection is made when any of 0.1 s to 999.8 s is set in Pr. 1432. In order to enable the
signal loss detection, data must be sent by connected devices at an interval equal to or less than
the time set for the communication check. (The inverter makes a communication check (clearing
of communication check counter) regardless of the station number setting of the data sent from
the master.)
●
Communication check is started at the first communication when the inverter operates in the
Network operation mode and the command source is specified as communication via the Ether-
net connector.
Pr.1431 setting
Description
Operation panel display/
indicator
LF signal output
0 (initial value)
Detection disabled
—
No
1
Warning output
EHR
No
2
Warning and alarm output
EHR
Yes
3
Protective function (E.EHR)
E.EHR
Yes
Tab. 5-278:
Pr. 1431 settings
Example
When Pr. 1432 = 0.1 to 999.8 s
I003114A
Fig. 5-255:
Timing chart for Ethernet communication check time interval
E.EHR
External
Operation mode
Fault (E.EHR)
Network
OFF
ON
Communication
check counter
Connected device
Time
Inverter
Inverter
Connected device
Pr. 1432
Check starts
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......