(G) Control parameters
Parameters
5 - 546
Setting of operation time (X13 signal, Pr. 11)
●
Set the time applying the DC injection brake to Pr. 11 "DC injection brake operation time".
●
When the motor does not stop due to large load moment (J), increasing the setting produces an
effect.
●
When Pr. 11 = "0 s", DC injection brake will not operate. (The motor will coast to stop.)
●
When Pr. 11 = "8888", DC injection brake will operate when the X13 signal is turned ON. DC
injection brake will operate when the X13 signal is turned ON even while operating.
●
For the X13 signal input, set "13" in any of Pr. 178 to Pr. 189 to assign the function.
Fig. 5-265:
When Pr. 11 is set to "8888"
I001559E
NOTE
The X13 signal is disabled during PM motor control.
Output fr
equenc
y
[H
z]
DC injection
brake
voltage
Time
ON
Pr. 12
X13
Time
OFF
STF
ON
ON
When Pr. 11 = "8888"
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......