Basic operation
Basic operation procedure (PU operation)
FR-F800
4 - 21
NOTES
Pr. 184 "AU terminal function selection" must be set to "4" (AU signal) (initial value).
To change the frequency (60 Hz) at the maximum current input (initial value 20 mA), adjust Pr. 126
"Terminal 4 frequency setting gain frequency".
To change the frequency (0 Hz) at the minimum current input (initial value 4 mA), adjust the cali-
bration parameter C5 "Terminal 4 frequency setting bias frequency".
Parameters referred to
Pr. 7
Acceleration time
=>
Pr. 8
Deceleration time
=>
Pr. 79
Operation mode selection
=>
Pr. 126
Terminal 4 frequency setting gain frequency
=>
Pr. 184
AU terminal function selection
=>
C5 (Pr. 904)
Terminal 4 frequency setting bias frequency
=>
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......