Parameters
(D) Operation command and frequency command
FR-F800
5 - 141
Selection of pulse train input (Pr. 291)
●
Setting Pr. 291 "Pulse train I/O selection" = "1, 11, 21, 100" and Pr. 384 "Input pulse division scaling
factor"
≠
"0" changes the function of terminal JOG to a pulse train input so that the frequency can
be set to the inverter. In the initial setting, the JOG signal is assigned to terminal JOG. A maximum
pulse train of 100k pulses/s can be input.
●
Connection with an open collector output system pulse generator
When the wiring length is long with open collector outputs, the influence of stray capacitance
causes the pulse to flatten out and prevents the input pulse from being recognized.
When the wiring length is long (10 m or longer of shielded twisted pair cable with a recommended
cable gauge of 0.75 mm²), connect the open collector output signal to the power supply by an
external pull-up resistance. The table below shows the reference resistance values for wiring
length. The stray capacitance of the wiring changes considerably according to how the cable is
laid, thus the above wiring lengths are not guaranteed values. When using a pull-up/down
resistance, check the permissible load of the resistor and the permissible load current of the output
transistor, and use within the permissible range.
●
Connection with a complementary output system pulse generator
I002573E_G
Fig. 5-37:
Pulse train input
Wiring length
Less than 10 m
10 to 50 m
50 to 100 m
Pull-up/down resistance
Not required
1 kΩ
470 Ω
Load current (reference)
10 mA
35 mA
65 mA
Tab. 5-63:
Resistance values for pull up and pull down resistances
I002574E_G
Fig. 5-38:
Pulse generator output
NOTES
When pulse train input is selected, the function assigned to terminal JOG by Pr. 185 "JOG terminal
function selection" is invalid.
Pr. 291 is the selection parameter for pulse train output/FM output. Thus, before changing the set-
ting, check the specifications of the device connected to the terminal FM. (For the pulse train out-
put, refer to page 5-216.)
Source logic
Inverter
Pull up resistance
Pull down resistance
Sink logic
2 k
Inverter
PC
JOG
SD
JOG
PC
2 k
SD
Inverter
Source logic
24 V
power
JOG
PC
SD
2 k
24 V
power
JOG
PC
SD
2 k
Inverter
Sink logic
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......