(M) Monitor display and monitor output signal
Parameters
5 - 218
5.8.4
Adjusting terminals FM/CA and AM
By using the operation panel or the parameter unit, terminals FM, CA and AM can be adjusted (cali-
brated) to the full scale.
The parameter number in parentheses ( ) is the one for use with the LCD operation panel and the
parameter unit (FR-PU07).
NOTES
Terminal JOG input specifications (pulse train input or contact input) can be selected with Pr. 291.
When changing the setting value, be careful not to change the terminal JOG input specifications.
(Refer to page 5-140 for pulse train input.)
Connect a meter between the terminals FM and SD after changing the Pr. 291 setting value. When
using the pulse train of FM output (voltage output), be careful that voltage is not added to termi-
nal FM.
A connection cannot be made to the pulse input of a source logic type.
If all parameter clear is performed when selecting the high-speed pulse train output (Pr. 291 = "10,
11, 20, 21, 100"), the terminal FM output can be changed from high-speed pulse train output to
FM output (voltage output), since the Pr. 291 setting value returns to the initial value of "0".
Perform all parameter clear after removing the device connected to the terminal FM.
Pr.
Name
Initial value
Setting range
Description
C0 (900)
M310
FM/CA terminal calibration
⎯
⎯
Calibrates the scale of the meter
connected to terminals FM and CA.
C1 (901)
M320
AM terminal calibration
⎯
⎯
Calibrates the scale of the analog
meter connected to terminal AM.
C8 (930)
M330
Current output bypass signal
0%
0 to 100%
Set the signal value at the minimum
analog current output.
C9 (930)
M331
Current output bypass current
0%
0 to 100%
Set the current value at the
minimum analog current output.
C10 (931)
M332
Current output gain signal
100%
0 to 100%
Sets the signal value when the
analog current output is at
maximum.
C11 (931)
M333
Current output gain current
100%
0 to 100%
Set the current value at the
maximum analog current output.
867
M321
AM output filter
0.01 s
0 to 5 s
Set the terminal AM output filter.
869
M334
Current output filter
0.01 s
0 to 5 s
Set the terminal AM output filter.
0, 1
10, 11,
20, 21, 100
FM output circuit
3.3 k
8.2 V
Pr. 291
Terminal FM
Open collector output circuit
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......