Parameters
(H) Protective function parameter
FR-F800
5 - 169
Emergency drive execution sequence
●
Operation of the emergency drive function (when the switchover to the commercial power supply
during emergency drive is disabled, and the retry in case of critical faults is selected)
NOTES
When X84 signal is ON for 3 s, the emergency drive is executed.
Y65 signal turns ON during emergency drive operation.
"ED" appears on the operation panel during emergency drive operation.
ALM3 signal turns ON when a fault occurs during emergency drive operation.
I003023E
Fig. 5-59:
Emergency drive function when switchover to the commercial power supply is disabled
RES
X84
STF
ALM3
Y65
ALM
Retry waiting time
Pr. 514
Emergency drive continued
Frequency
Time
Retry in case of critical faults
Continuous operation except in case of critical faults
Normal operation
Emergency drive in operation
Motor rotations per minute
Pr. 524
Coasting
Emergency drive finished
ON
ON
ON
ON
ON
ON
ON
3 s
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......