Parameters
(M) Monitor display and monitor output signal
FR-F800
5 - 243
Speed detection hysteresis (Pr. 870)
This function prevents chattering of the speed detection signals. When an output frequency fluctu-
ates, the up to frequency signal (SU) and the speed detection signals (FB and FB2) may repeat ON/OFF
(chatter).
Setting hysteresis to the detected frequency prevents chattering of these signals.
Fig. 5-99:
Example of the speed detection (FB) signal
I002629E
I003032E
Fig. 5-100:
Example of the up to frequency (SU) signal
NOTES
In the initial setting, the FU signal is assigned to the terminal FU, and the SU signal is assigned to
the terminal SU.
All signals turn OFF during DC injection brake, and tuning at start-up.
Each signal's reference frequency differs by the control method.
Setting a higher value in Pr. 870 slows the response of frequency detection signals (SU, FB, FB2).
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 190 to Pr. 196
(output terminal function selection)
=>
FB
Pr. 42
OFF
OFF
ON
ON
ON
Output
frequency
(Hz)
Pr. 870
Pr. 41
Time
Output
frequency
(Hz)
SU output level
Set frequency
SU output level
SU signal
Pr. 870
Pr. 870
Pr. 870
Pr. 870
ON
ON
ON
Control method
Compared frequency
FU, FU2
FB, FB2, SU
V/F control
Output frequency
Output frequency
Advanced magnetic flux vector
control
Output frequency before the slip
compensation
Output frequency before the slip
compensation
PM motor control
Frequency command value
Estimated frequency (actual motor
speed)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......