![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 655](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886655.webp)
Parameters
(N) Operation via communication and its settings
FR-F800
5 - 483
Refer to page 5-470 for data formats (A, A1, A2, B, C, C1, D, E, E1, E2, E3, F)
Turning OFF the power supply while clearing parameters with H5A5A or H55AA returns the
communication parameter settings to the initial settings.
Refer to the calibration parameter list below for details on calibration parameters.
The gain frequency can be also written using Pr. 125 (instruction code: H99) or Pr. 126 (instruction
code: H9A).
To read/write C3 (Pr. 902) or C6 (Pr. 904) after inverter reset or parameter clear, execute from (
)
again.
In
v
e
rt
er model monitor
Inverter
model
Read
H7C
Reading inverter model in ASCII code.
"H20" (blank code) is set for blank area
Example of "FR-F840-1 (FM type)"
H46, H52, H2D, H46, H38, H34, H30, H2D, H31, H20, H20 ....H20
20 digits
(B, E3/D)
Capacity
Read
H7D
Reading inverter ND rated capacity in ASCII code.
Data is read in increments of 0.1kW, and rounds down to
0.01kW increments
"H20" (blank code) is set for blank area
Example:
0.75K ................ " 7" (H20, H20, H20, H20, H20, H37)
6 digits
(B, E2/D)
NOTES
Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
For the instruction codes HFF, HEC and HF3, their values are held once written but cleared to zero
when an inverter reset or all clear is performed.
When a 32-bit parameter setting or monitored value is read and the read value exceeds HFFFF, the
reply data will be HFFFF.
Example
When reading the C3 (Pr. 902) and C6 (Pr. 904) settings from the inverter of station No. 0.
Computer send data
Inverter send data
Description
ENQ 00 FF 0 01 70
ACK 00
Set "H01" in the extended link parameter
ENQ 00 EC 0 01 79
ACK 00
Set "H01" in second parameter changing
ENQ 00 5E 0 0A
STX 00 0000 ETX 20
C3 (Pr. 902) is read. 0% is read.
ENQ 00 60 0 F6
STX 00 0000 ETX 20
C6 (Pr. 904) is read. 0% is read.
Tab. 5-236:
Example for data transmission
Item
Read/
Write
Instruc-
tion
code
Data description
Number of
data digits
(Format)
Tab. 5-235:
Setting of the instruction codes and data (3)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......