Parameters
(H) Protective function parameter
FR-F800
5 - 173
MC operation
: MC-ON
×: MC-OFF
—: During inverter operation, MC2-OFF, MC3-ON
During commercial power supply operation, MC2-ON, MC3-OFF
Invariance: The status before changing the signal ON or OFF is held.
PID control during emergency drive operation
●
During emergency drive operation in the PID control mode, the operation is performed under PID
control using the Pr. 524 setting as a set point. Input the measured values in the method set in
Pr. 128 or Pr. 753.
●
When the PID control mode is selected for emergency drive, the PID action during emergency
drive operation is as follows depending on the PID control setting.
●
While the "retry" (Pr. 523 = "22
, 32
") is selected in the PID control mode, if a retry occurs at an
occurrence of E.CPU, E.1 to E.3, E.5 to E.7 during emergency drive operation, the operation is
performed not under PID control but with the fixed frequency. Use Pr. 1013 "Running speed after
emergency drive retry reset" to set the fixed frequency.
NOTE
During electronic bypass operation while the electronic bypass sequence is enabled (Pr. 135 = "1"),
the emergency drive function is not available.
Item
PID control action
Set point / measured value
input setting
Deviation input setting
Without PID control setting
Measured value input
selection
Held
Terminal 4 input
Terminal 4 input
Forward action /
reverse action selection
Held
Held
Reverse action (initial setting)
Proportional band
Held
Held
100% (initial setting)
Integral time
Held
Held
1 s (initial setting)
Differential time
Held
Held
Not used (initial setting)
Applied to the frequency /
calculation only
Applied to the frequency
Applied to the frequency
Applied to the frequency
Other PID-related settings
Held
Held
Held
Tab. 5-74:
Emergency drive operation depending on PID control setting
NOTE
For details of the PID control, refer to page 5-353.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......