![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 477](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886477.webp)
Parameters
(C) Motor constant parameters
FR-F800
5 - 305
For the FR-F820-02330(55K) or lower and FR-F840-01160(55K)or lower.
For the FR-F820-03160(75K) or higher and FR-F840-01800(75K)or higher.
Differs according to the voltage class. (200 V/400 V)
The setting range and unit change according to the Pr. 71 (Pr. 450) setting.
458
C220
Second motor
constant (R1)
9999
0 to 50 Ω, 9999
Tuning data of the second motor
(The value measured by offline auto tuning
is automatically set.)
9999:
Uses the constant value of Mitsubishi motor
(SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and
so on).
0 to 400 mΩ, 9999
459
C221
Second motor
constant (R2)
9999
0 to 50 Ω, 9999
0 to 400 mΩ, 9999
460
C222
Second motor
constant (L1) / d-axis
inductance (Ld)
9999
0 to 400 mH, 9999
461
C223
Second motor
constant (L2) / q-axis
inductance (Lq)
9999
0 to 6000 mH, 9999
0 to 400 mH, 9999
462
C224
Second motor
constant (X)
9999
0 to 100%, 9999
455
C225
Second motor
excitation current
9999
0 to 500 A, 9999
0 to 3600 A, 9999
860
C226
Second motor
torque current/
Rated PM motor
current
9999
0 to 500 A, 9999
0 to 3600 A, 9999
560
A712
Second frequency
search gain
9999
0 to 32767
The offline auto tuning automatically sets
the gain required for the frequency search
of the second motor.
9999
Uses the constant value of Mitsubishi motor
(SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and
so on).
NOTES
The function is enabled under Advanced magnetic flux vector control.
Even if a motor other than Mitsubishi standard motors (SF-JR 0.4 kW or higher), high-efficiency
motors (SF-HR 0.4 kW or higher), Mitsubishi constant-torque motors (SF-JRCA 4P, SF-HRCA 0.4 kW
to 55 kW), or Mitsubishi high-performance energy-serving motor (SF-PR), such as other manufac-
turers' induction motors, SF-JRC, SF-TH, etc., is used, or when the wiring length is long (approx. 30
m or longer), a motor can run with the optimum operation characteristics by using the offline auto
tuning function.
Tuning is enabled even when a load is connected to the motor.
During offline auto tuning, the motor rotation can be locked (Pr. 96 = "1") or unlocked (Pr. 96 =
"101"). The tuning is more accurate when the motor can rotate (unlocked).
Reading/writing of the motor constants tuned by offline auto tuning are enabled. The offline auto
tuning data (motor constants) can be copied to another inverter with the operation panel.
The offline auto tuning status can be monitored with the operation panel and the parameter unit.
Pr.
Name
Initial
value
Setting range
Description
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......