Ethernet communication (FR-F800-E)
Parameters
5 - 618
●
Input signals (inverter to master module)
Device No.
Signal
Description
RX0
Forward running
0 : Other than forward running (during stop or reverse rotation)
1 : Forward running
RX1
Reverse running
0 : Other than reverse running (during stop or forward rotation)
1 : Reverse running
RX2
Running (terminal RUN function)
Functions assigned to terminals RUN, SU, OL, IPF, FU, ABC1 and ABC2 activate.
Signal names are initial values. Using Pr. 190 to Pr. 196, you can change output
signal functions.
RX3
Up to frequency (terminal SU function)
RX4
Overload alarm (terminal OL function)
RX5
Instantaneous power failure (terminal
IPF function)
RX6
Frequency detection (terminal FU
function)
RX7
Fault (terminal ABC1 function)
RX8
— (terminal ABC2 function)
RX9
— (DO0 function)
Functions assigned to Pr. 313 to Pr. 315 are activated.
No signal is assigned in the initial setting. Use Pr.313 to Pr.315 to assign signals to
the devices RX9 to RXB. The setting range depends on the inverter. For details,
refer to the description of Pr. 190 to Pr. 196 (Output terminal function selection)
on page 5-231.
RXA
— (DO1 function)
RXB
— (DO2 function)
RXC
Monitoring
After "1" is set in the monitor command (RYC), and the monitored value is set in the
remote register Rwr0, 1, 4 to 7,, "1" is set in this signal. When "0" is set in the monitor
command (RYC), "0" is set in this signal.
RXD
Frequency setting completion (RAM)
After "1" is set in the frequency setting command (RYD) and the frequency setting
command is written to the inverter RAM, "1" is set in this signal.
When "0" is set in the frequency setting command (RYD), "0" is set in this signal.
RXE
Frequency setting completion (RAM,
EEPROM)
After "1" is set in the frequency setting command (RYE) and the frequency setting
command is written to the inverter RAM and EEPROM, "1" is set in this signal.
When "0" is set in the frequency setting command (RYE), "0" is set in this signal.
RXF
Instruction code execution completion
After "1" is set in the instruction code execution request (RYF) and the processes
corresponding to the instruction codes (RWw2, 10, 12, 14, 16, and 18) are executed,
"1" is set in this signal. When "0" is set in the instruction code execution request (RYF),
"0" is set in this signal.
RX1A
Error status flag
When an inverter error occurs (protective function is activated), "1" is set in this signal.
RX1B
Remote station ready
When the inverter goes into the ready status upon completion of initial setting after
power-ON or hardware reset, "1" is set in this signal. When an inverter error occurs
(protective function is activated), "0" is set in this signal. The signal is used as an
interlock signal during the write to/read from the master module.
Tab. 5-344:
Output signals from the inverter (input signals to master module)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......