(M) Monitor display and monitor output signal
Parameters
5 - 232
Output signal list
●
The functions of the output terminals can be set.
●
Refer to the following table and set each parameter.
Setting
Signal
name
Function
Operation
Related
parameter
Refer to
page
Positive
logic
Negative
logic
0
100
RUN
Inverter running
Output during operation when the
inverter output frequency reaches Pr. 13
"Starting frequency" or higher.
⎯
1
101
SU
Up to frequency
Output when the output frequency
reaches the set frequency.
Pr. 41
2
102
IPF
Instantaneous power
failure/undervoltage
Output when an instantaneous power
failure or undervoltage protection
operation occurs.
Pr. 57
3
103
OL
Overload warning
Output during operation of the stall
prevention function.
Pr. 22, Pr. 23,
Pr. 66, Pr. 148,
Pr. 149, Pr. 154
4
104
FU
Output frequency
detection
Output when the output frequency
reaches the frequency set in Pr. 42 (Pr. 43)
during reverse rotation) or higher.
Pr. 42, Pr. 43
5
105
FU2
Second output frequency
detection
Output when the output frequency
reaches the frequency set in Pr. 50 or
higher.
Pr. 50
7
107
For manufacturer setting. Do not set.
8
108
THP
Electronic thermal O/L
relay pre-alarm
Output when the cumulative electronic
thermal O/L relay value reaches 85% of
the trip level. (Electronic thermal O/L
relay protection (E.THT/E.THM) is
activated when the value reaches 100%.)
Pr. 9
10
110
PU
PU operation mode
Output when PU operation mode is
selected.
Pr. 79
11
111
RY
Inverter operation ready
Output when the reset process is
completed after powering ON the
inverter (when starting is possible by
switching the start signal ON or during
operation).
⎯
12
112
Y12
Output current detection
Output when the output current is
higher than the Pr. 150 setting for the
time set in Pr. 151 or longer.
Pr. 150, Pr. 151
13
113
Y13
Zero current detection
Output when the output current is lower
than the Pr. 152 setting for the time set in
Pr. 153 or longer.
Pr. 152, Pr. 153
14
114
FDN
PID lower limit
Output when the value is lower than the
lower limit of PID control.
Pr. 127 to
Pr. 134,
Pr. 575 to
Pr. 577, Pr.1370
15
115
FUP
PID upper limit
Output when the value is higher than the
upper limit of PID control.
16
116
RL
PID forward/reverse
rotation output
Output during forward rotation under
PID control.
17
⎯
MC1
Electronic bypass MC1
Used when using the electronic bypass
function.
Pr. 135 to
Pr. 139, Pr. 159
18
⎯
MC2
Electronic bypass MC2
19
⎯
MC3
Electronic bypass MC3
25
125
FAN
Fan fault output
Output when a fan fault occurs.
Pr. 244
26
126
FIN
Heatsink overheat pre-
alarm
Output when the heatsink temperature
reaches about 85% of the heatsink
overheat protection operation
temperature.
⎯
35
135
TU
Torque detection
Output when the motor torque is higher
than the Pr. 864 setting.
Pr. 864
39
139
Y39
Start time tuning
completion
Output when tuning is completed during
start-up.
Pr. 95, Pr. 574
Tab. 5-101:
Output terminal function assignment (1)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......