(M) Monitor display and monitor output signal
Parameters
5 - 236
Take caution when changing the frequency setting with an analog signal or the setting dial of the
operation panel (FR-DU08), because this change speed and the timing of the change speed
determined by the acceleration/deceleration time setting may cause the output of the SU (up to
frequency) signal to switch repeatedly between ON and OFF. (This repeating does not occur when
the acceleration/deceleration time setting is "0 s".)
The setting is available only for standard models.
This signal cannot be assigned to the output terminals for plug-in options (FR-A8AY, FR-A8AR).
Available when the plug-in option is connected.
!
This can be set for Pr. 313 to Pr. 322 when an option (FR-A8AY, FR-A8AR, FR-A8NC, or FR-A8NCE) is
installed. For the corresponding parameters of each option, refer to the Instruction Manual of the
option.
When the power is reset, the fault output 2 signal (ALM2) turns OFF at the same time as the power
turns OFF.
$
FR-F800-E only.
217
317
Y217
Priming pump operation
Outputs the signal for starting the
priming pump.
Pr.1363
218
318
STIR
Stirring
Output during the stirring operation.
Pr.1364, Pr.1365
219
319
Y219
PID upper/lower limit
pre-warning
Output when the PID measured value
meets the requirements of the limit pre-
warning signal output conditions.
Pr.1370 to
Pr.1373
220
320
Y220
Second PID upper/lower
limit pre-warning
226
326
Y226
Auxiliary pressure pump
operation
Output when the PID deviation exceeds
the auxiliary pressure pump operation
starting level.
Pr.1374, Pr.1375
228
328
DRY
Dry run
Output when a dry-run state is detected.
Pr.42, Pr.43,
Pr.132, Pr.1144,
Pr.1370
229
329
Y229
PID input pressure
warning
Output when the pump inlet pressure
reaches the warning level.
Pr.1370,
Pr.1373,
Pr.1377,
Pr.1378, Pr.1380
230
330
Y230
PID input pressure fault
Output when the pump inlet pressure
reaches the fault level.
Pr.1370,
Pr.1377,
Pr.1379, Pr.1381
242
342
LNK
Inverter-to-inverter
linkup signal
Available to check that the master-slave
communication is established.
Pr. 1124,
Pr. 1125
9999
⎯
No function
⎯
⎯
⎯
NOTES
The same function may be set to more than one terminal
The terminal conducts during function operation when the setting is "0 to 99, 200 to 299", and
does not conduct when the setting is "100 to 199, 300 to 399".
When Pr. 76 "Fault code output selection" = "1", the output signals of terminals SU, IPF, OL and FU
operate according to Pr. 76 setting. (When the inverter's protective function is activated, the signal
output switches to fault code output.)
The outputs of terminal RUN and the fault output relay are assigned according to the settings
above, regardless of Pr. 76.
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Setting
Signal
name
Function
Operation
Related
parameter
Refer to
page
Positive
logic
Negative
logic
Tab. 5-101:
Output terminal function assignment (5)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......