(N) Operation via communication and its settings
Parameters
5 - 492
Function code list
Function
name
Read/
Write
Code
Outline
Broadcast
communica-
tion
Message
format
reference
page
Read holding
register
Read
H03
The data of the holding registers is read.
The various data of the inverter can be read from
MODBUS® registers.
System environmental variable (Refer to page 5-499.)
Real time monitor (Refer to page 5-199.)
Faults history (Refer to page 5-503.)
Model information monitor (Refer to page 5-503.)
Inverter parameters (Refer to page 5-501.)
Not available
Preset single
register
Write
H06
Data is written to holding registers.
Data can be written to MODBUS® registers to output
instructions to the inverter or set parameters.
System environmental variable (Refer to page 5-499.)
Inverter parameters (Refer to page 5-501.)
Available
Diagnostics
Read
H08
Functions are diagnosed. (communication check only)
A communication check can be made since the query
message is sent and the query message is returned as
it is as the return message (subfunction code H00
function).
Subfunction code H00 (Return Query Data)
Not available
Preset multiple
registers
Write
H10
Data is written to consecutive multiple holding
registers.
Data can be written to consecutive multiple
MODBUS® registers to output instructions to the
inverter or set parameters.
System environmental variable (Refer to page 5-499.)
Inverter parameters (Refer to page 5-501.)
Available
Read holding
register access
log
Read
H46
The number of registers that were successfully
accessed by the previous communication is read.
Queries by function codes H03 and H10 are
supported.
The number and start address of holding registers
successfully accessed by the previous communication
are returned.
"0" is returned for both the number and start address
for queries other than function code H03 and H10.
Not available
Tab. 5-243:
Function code list
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......