Ethernet communication (FR-F800-E)
Parameters
5 - 634
5.18.5 Instructions
Operating and handling instructions
●
The inverter only accepts the commands from the programmable controller during operation
using the CC-Link IE Field Network Basic. The run command from external and parameter unit is
ignored.
●
If different inverters have the same station number, the communication cannot be performed
properly.
●
The inverter protective function (E.EHR) is activated if data communication stops for more than
the time set in Pr. 1432 "Ethernet communication check time interval" due to a programmable
controller fault, a break in the Ethernet cable etc. during operation through CC-Link IE Field
Network Basic.
●
If the programmable controller (master station) is reset during CC-Link IE Field Network Basic
operation or if the programmable controller is powered OFF, data communication stops and the
inverter protective function (E.EHR) is activated.
To reset the programmable controller (master station), switch the operation mode to the External
operation once, then reset the programmable controller.
●
When Pr. 340 = "0 (initial value)", any inverter whose main power is restored is reset to return to
the External operation mode. To resume the Network operation, therefore, set the operation mode
to the Network operation using the programmable controller program.
Set a value other than "0" in Pr. 340 to start in the Network operation mode after inverter reset.
For the details of Pr. 340 refer to page 5-128.
Troubleshooting
Description
Check point
Operation mode does not switch to
the Network operation mode
Check that the Ethernet cable is installed correctly.
(Check for contact fault, break in the cable, etc.)
Check that the inverter is in the External operation mode.
Check that the operation mode switching program is running.
Check that the operation mode switching program has been written correctly.
Inverter does not start in the
Network operation mode
Check that the inverter starting program is running.
Check that the inverter starting program has been written correctly.
Check that Pr. 338 "Communication operation command source" is not set to
External.
Tab. 5-351:
Error descriptions and troubleshooting
Parameters referred to
Pr. 37
Speed display
=>
Pr. 144
Speed setting switchover
=>
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......