(A) Application parameters
Parameters
5 - 444
Operation outline
●
This function samples the status (analog monitor and digital monitor) of the inverter, traces the
sampling data when a trigger (trace start condition) is generated, and saves the resulting trace
data.
●
When the trace function is set enabled, samplings are collected and the inverter goes into the
pre-trigger status.
●
In the pre-trigger status, samples are collected, and the trigger standby status is entered when
sufficient samples for the number of pre-trigger samples have been collected.
●
When the trigger is generated in the trigger standby status, the trace is started and the trace data
is saved.
1038
A930
Digital source selection
(1ch)
1
1 to 255
Select the digital data (I/O signal) to be sampled on
each channel.
1039
A931
Digital source selection
(2ch)
2
1040
A932
Digital source selection
(3ch)
3
1041
A933
Digital source selection
(4ch)
4
1042
A934
Digital source selection
(5ch)
5
1043
A935
Digital source selection
(6ch)
6
1044
A936
Digital source selection
(7ch)
7
1045
A937
Digital source selection
(8ch)
8
1046
A938
Digital trigger channel
1
1 to 8
Select the digital channel to be the trigger.
1047
A939
Digital trigger operation
selection
0
0
Trace starts when the signal turns ON
1
Trace starts when the signal turns OFF
I002723E
Fig. 5-219:
Trace function
Pr.
Name
Initial
value
Setting
range
Description
0%
90%
0%
90%
100%
0%
90%
100%
Sampling start
Sampling data
If the data is short for the pre-trigger sampling,
the inverter goes into the pre-trigger state.
Pre-trigger sampling number
Data in the period
is discarded.
Sampling start
Sampling data
Sampling data
Sampling start
Data in the period
is discarded.
Trace start
Once the enough data is collected for trigger sampling,
the inverter goes into the trigger-ready state.
At trigger generation, samples equivalent to the 100 %
pre-trigger sampling number are collected and saved.
Pre-trigger sampling number
A trigger occurs
Trace completed
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......