![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 875](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886875.webp)
Specifications
Inverter rating
FR-F800
8 - 1
8
Specifications
8.1 Inverter
rating
8.1.1 200
V
class
For footnotes
to
$
refer to page 8-3.
Model FR-F820-
00046
(0.75K)
00077
(1.5K)
00105
(2.2K)
00167
(3.7K)
00250
(5.5K)
00340
(7.5K)
00490
(11K)
00630
(15K)
00770
(18.5K)
00930
(22K)
01250
(30K)
01540
(37K)
01870
(45K)
02330
(55K)
03160
(75K)
03800
(90K)
04750
(110K)
Applicable motor capacity
[kW]
SLD
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
110
132
LD
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
Outp
ut
Rated capacity [kVA]
SLD
1.8
2.9
4
6.4
10
13
19
24
29
35
48
59
71
89
120
145
181
LD
1.6
2.7
3.7
5.8
8.8
12
17
22
27
32
43
53
65
81
110
132
165
Rated current [A]
SLD
4.6
7.7
10.5
16.7
25
34
49
63
77
93
125
154
187
233
316
380
475
LD
4.2
7
9.6
15.2
23
31
45
58
70.5
85
114
140
170
212
288
346
432
Overload current rating
SLD
110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature of 40 °C
LD
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature of 50 °C
Rated voltage
Three-phase 200 to 240 V
Po
w
er
su
pp
ly
Rated input AC voltage/frequency
Three-phase 200 to 240 V 50 Hz/60 Hz
Permissible AC voltage fluctuation
170 to 264 V 50 Hz/60 Hz
Permissible frequency fluctuation
±5%
Rated input current
[A]
!
SLD
5.3
8.9
13.2
19.7
31.3
45.1
62.8
80.6
96.7
115 151 185
221
269
316
380
475
LD
5
8.3
12.2
18.3
28.5
41.6
58.2
74.8
90.9
106 139 178 207 255 288
346
432
Power supply capacity
[kVA]
SLD
2
3.4
5
7.5
12
17
24
31
37
44
58
70
84
103
120
145
181
LD
1.9
3.2
4.7
7
11
16
22
29
35
41
53
68
79
97
110
132
165
Protective structure (IEC 60529)
$
Enclose type (IP20)
Open type (IP00)
Cooling system
Self-cooling
Forced air cooling
Approx. mass [kg]
1.9
2.1
3.0
3.0
3.0
6.3
6.3
8.3
15
15
15
22
42
42
54
74
74
Tab. 8-1:
Specifications FR-F820
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......