Parameters
(A) Application parameters
FR-F800
5 - 365
When each of Pr. 131, Pr. 132 and Pr. 553 corresponding to each of the FUP, FDN and Y48 signals is
set to "9999" (function not activated), signal output and protective function are disabled.
At the same time with the signal output, the protective function (E.PID) is activated.
At the same time with the signal output, deceleration is performed using the normal deceleration
time. After the deceleration stop, the protective function (E.PID) is activated.
At the same time with the signal output, deceleration is performed using the normal deceleration
time. When the measured value returns to normal, operation can be restarted.
●
Example chart
Protective function (E.PID) activation at the same time with the signal output (Pr. 554 = "1, 3, 11,
or 13") / Protective function activation after the deceleration stop (Pr. 554 = "4, 6, 14, or 16") (reverse
action)
●
Example chart:
Deceleration stop (restart) at the signal output (Pr. 554 = "5, 7, 15, or 17") (reverse action)
I003041
Fig. 5-169:
Example chart of protective function activation
I003042E
Fig. 5-170:
Example chart of deceleration stop (restart)
E.PID
Pr.1370
Pr.1370
Pr.1370
Pr.1370
Pr.1370
Pr.1370
FUP
FDN
E.PID
Measured value
Pr. 1370
Output
frequency [Hz]
Time
Upper limit level
Pr.131 (Pr.1143)
Measured
value
Pr. 1370
Pr. 1370
ON
Deceleration stop
(Pr. 554 = "4, 6, 14, 16")
Output shutoff
(Pr. 554 = "1, 3, 11, 13")
Lower limit level
Pr.132 (Pr.1144)
Pr.1370
Pr.1370
Pr.1370
Pr.1370
Pr.1370
Pr.1370
FUP
FDN
Deceleration stop when the
measured value reaches or
exceeds the upper limit.
Deceleration stop when the
measured value reaches or
exceeds the upper limit.
Measured value
Pr. 1370
Output
frequency [Hz]
Time
Upper limit level
Pr.131 (Pr.1143)
Measured value
Pr. 1370
Pr. 1370
ON
Operation can be
restarted when the
measured value exceeds
the upper limit.
Operation is continued when
the measured value reaches or
falls below the lower limit.
Lower limit level
Pr.132 (Pr.1144)
Deceleration stop when the
measured value reaches or
exceeds the upper limit.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......