(G) Control parameters
Parameters
5 - 556
DC feeding mode 1 (Pr. 30 = "10, 11") (Standard models)
●
For standard models, setting Pr. 30 = "10 or 11" allows operation with a DC power supply.
●
Do not connect anything to the AC power supply connecting terminals R/L1, S/L2, and T/L3, and
connect the DC power supply to the terminals P/+ and N/-. Also, remove the jumpers between
terminal R/L1 and R/L11as well as between S/L2 and S1/L21, and connect the terminals R1/L11
and S1/L21 to the terminals P/+ and N/-.
●
Following is a connection example.
DC feeding mode 2 (Pr. 30 = "20, 21") (Standard models)
●
When Pr. 30 = "20, 21", it will normally operate with AC power supply and operate with DC power
supply such as batteries at the time of power failure.
●
Connect the AC power supply to the AC power supply connecting terminals R/L1, S/L2, and T/L3,
and connect the DC power supply to the terminals P/+ and N/-. Also, remove the jumpers between
terminal R/L1 and R/L11as well as between S/L2 and S1/L21, and connect the terminals R1/L11
and S1/L21 to the terminals P/+ and N/-.
●
Operation with DC current is possible by turning ON the DC feeding operation permission signal
(X70). For details on I/O signal, refer to following table.
I002757E_G
Fig. 5-271:
Connection example for DC feeding mode 1
E
CAUTION:
Do not connect a separated converter type inverter to a DC power supply. Doing so may damage
the inverter.
R/L1
S/L2
T/L3
U
V
W
P/+
N/-
STF
STR
PC
R1/L11
S1/L21
10
2
2
3
1
5
(+)
(-)
MC
Inverter
Inrush
current
limit circuit
DC power
Forward rotation start
Reverse rotation start
Contact input common
Frequency command
Frequency setting
potentiometer
1/2W 1 k
Earth
(Ground)
IM
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......