![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 841](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886841.webp)
Protective functions
Causes and corrective actions
FR-F800
6 - 29
Operation panel
indication
E.USB
FR-LU08
USB comm error
Name
USB communication fault
Description
The inverter trips when the communication is cut off for the time set in Pr. 548 "USB
communication check time interval".
Check point
Check that the USB communication cable is connected securely.
Corrective action
Check the Pr. 548 setting.
Connect the USB communication cable securely.
Increase the Pr. 548 setting or set "9999." (Refer to page 5-531.)
Operation panel
indication
E.SAF
FR-LU08
Safety circuit fault
Name
Safety circuit fault
Description
The inverter trips when a safety circuit fault occurs.
The inverter trips if the either of the wire between S1 and SIC or S2 and SIC becomes non-
conductive while using the safety stop function.
When not using the safety stop function, the inverter trips when the shorting wire between
terminals S1 and PC or across S2 and PC is disconnected.
Check point
Check that the safety relay module or the connection has no fault when using the safety
stop function.
Check if the shorting wire between S1 and PC or between S2 and PC is disconnected when
not using the safety stop function.
Corrective action
When using the safety stop function, check that wiring of terminal S1, S2 and SIC is correct
and the safety stop input signal source such as a safety relay module is operating properly.
Refer to the Safety stop function instruction manual for causes and countermeasures.
(Please contact your sales representative for the manual.)
When not using the safety stop function, short across terminals S1 and PC and across S2 and
PC with shorting wires. (Refer to page 2-64.)
Operation panel
indication
E.PBT
FR-LU08
PBT fault
E.13
Intrnl circuit fault
E.BE
Brake transistor err
Name
Internal circuit fault
Description
The inverter trips when an internal circuit fault occurs.
Corrective action
Please contact your sales representative.
Operation panel
indication
E.OS
FR-LU08
Overspeed
occurrence
Name
Overspeed occurrence
Description
The inverter trips when the motor speed exceeds the Pr. 374 "Overspeed detection level" under
PM motor control. This protective function is not available in the initial status.
Check point
Check that the Pr. 374 setting is correct.
Corrective action
Set the Pr. 374 correctly.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......