Parameters
(A) Application parameters
FR-F800
5 - 335
Be careful of the capacity of the sequence output terminals.
The applied terminals differ by the settings of Pr. 190 to Pr. 196 (output terminal function selection).
When connecting a DC power supply, insert a protective diode.
When connecting an AC power supply, use the relay output option (FR-A8AR) and use contact
outputs.
The applied terminals differ by the settings of Pr. 180 to Pr. 189 (input terminal function selection).
To use the signal, assign the function to the output terminal Pr. 190 to Pr. 195 (output terminal
function selection) of the converter unit. It is recommended, that the wiring of the ALM signal is
always proof against wire breaks. High signal = no fault.
●
Operation of magnetic contactor (MC1, MC2, MC3)
Output terminal capacity
Output terminal permissible load
Open collector output of inverter (RUN, SU, IPF, OL, FU)
24 V DC 0.1 A
Inverter relay output (A1-C1, B1-C1, A2-B2, B2-C2)
Relay output option (FR-A8AR)
230 V AC 0.3 A
30 V DC 0.3 A
NOTES
Use the electronic bypass function in External operation mode. In addition, the wiring terminals
R1/L11 and S1/L21 must be connected to a separate power source that does go through MC1. Be
sure to connect using a separate power supply.
Be sure to provide a mechanical interlock for MC2 and MC3.
Magnetic
contactor
Installation location
Operation
During commercial
power supply
operation
During inverter
operation
During inverter fault
MC1
Between power supply and
inverter input side
Shorted
Shorted
Open
(short by reset)
MC2
Between power supply and
motor
Shorted
Open
Open
(Selected by Pr. 138.
Always open when the
external thermal relay is
operating.)
MC3
Between inverter output side
and motor
Open
Shorted
Open
Tab. 5-157:
Operations of magnetic contactors
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......