Causes and corrective actions
Protective functions
6 - 24
Operation panel
indication
E.LF
FR-LU08
Output phase loss
Name
Output phase loss
Description
The inverter trips if one of the three phases (U, V, W) on the inverter's output side (load side) is
lost.
Check point
Check the wiring. (Check that the motor is normally operating.)
Check that the capacity of the motor used is not smaller than that of the inverter.
Check if a start command is given to the inverter while the motor is coasting.
(PM motor control)
Corrective action
Wire the cables properly.
Input a start command after the motor stops. Alternatively, use the automatic restart after
instantaneous power failure/flying start function (page 5-423).
(PM motor control)
Operation panel
indication
E.OHT
FR-LU08
Ext TH relay oper
Name
External thermal relay operation
Description
The inverter trips if the external thermal relay provided for motor overheat protection or the
internally mounted thermal relay in the motor, etc. switches ON (contacts open).
This function is available when "7" (OH signal) is set in any of Pr. 178 to Pr. 189 (input terminal
function selection). This protective function is not available in the initial status. (OH signal is not
assigned.)
Check point
Check for motor overheating.
Check that the value "7" (OH signal) is set correctly to any of Pr. 178 to Pr. 189 (input terminal
function selection).
Corrective action
Reduce the load and operation duty.
Even if the relay contacts are reset automatically, the inverter will not restart unless it is reset.
Operation panel
indication
E.PTC
FR-LU08
PTC thermistor oper
Name
PTC thermistor operation
Description
The inverter trips if resistance of the PTC thermistor connected between the terminal 2 and
terminal 10 is equal to or higher than the Pr. 561 "PTC thermistor protection level" setting for a
continuous time equal to or longer than the setting value in Pr. 1016 "PTC thermistor protection
detection time". When the initial value (Pr. 561 = "9999") is set, this protective function is not
available.
Check point
Check the connection with the PTC thermistor.
Check the Pr. 561, Pr. 1016 setting.
Check the motor for operation under overload.
Corrective action
Reduce the load.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......