(A) Application parameters
Parameters
5 - 368
PID monitor function
●
This function displays the PID control set point, measured value and deviation on the operation
panel, and can output these from the terminals FM, AM and CA.
●
An integral value indicating a negative % can be displayed on the deviation monitor. 0% is
displayed as 1000. (These values cannot be output on the deviation monitor from terminals FM
and CA.)
●
Set the following values to Pr. 52 "Operation panel main monitor selection", Pr. 774 to Pr. 776
(Operation panel monitor selection), Pr. 992 "Operation panel setting dial push monitor selection",
Pr. 54 "FM/CA terminal function selection" and Pr. 158 "AM terminal function selection" for each
monitor.
When C42 (Pr. 934) and C44 (Pr. 935) are set, the minimum increment changes from unit % to no
unit, and the monitor range can be changed. (Refer to page 5-381.)
When the minus value display is set disabled using Pr. 290, the terminal AM output becomes "0".
Adjustment procedure
Parameter
settings
Monitor
description
Minimum
increment
Monitor range
Remarks
Terminal
FM/CA
Terminal
AM
Operation
panel
52
PID set point
0.1%
"0" is displayed at all times when
PID control is based in deviation
input.
92
Second PID set
point
53
PID measured value
0.1%
93
Second PID
measured value
67
PID measured value
2
0.1%
Displays PID measured value even
if PID control operating conditions
are not satisfied while the PID
control is enabled.
"0" is displayed at all times when
PID control is based in deviation
input.
95
Second PID
measured value 2
54
PID deviation
0.1%
Setting not
available
–100% to
900% to
1100% or
–100% to
100%
Using Pr. 290 "Monitor negative
output selection", minus values
can be output to the terminal AM
and displayed on the operation
panel.
Even if minus display is enabled,
the display range is 900% to
1100% in monitors on the
operation panel.
(0% is offset and displayed as
1000%.)
94
Second PID
deviation
91
PID manipulated
variable
0.1%
Setting not
available
–100% to
100%
900% to
1100% or
–100% to
100%
96
Second PID
manipulated
variable
Tab. 5-176:
PID monitor function
Enable PID control
When Pr. 128
≠
"0", PID control is enabled.
Set the set point, measured value and deviation input methods at Pr. 128, Pr. 609 and
Pr. 610.
Setting the parameter
Adjust the PID control parameters of Pr. 127, Pr. 129 to Pr. 134, Pr. 553, Pr. 554, Pr. 575
to Pr. 577.
PID gain tuning
Pr. 129, Pr. 130 and Pr. 134 are adjusted automatically by PID gain tuning.
(Refer to page 5-373.)
Terminal setting
Set the I/O terminals for PID control. (Pr. 178 to Pr. 189 (input terminal function
selection), Pr. 190 to Pr. 196 (output terminal function selection))
Turn the X14 signal ON
When the X14 signal is assigned to the input terminal, PID control is enabled by the
X14 signal turning ON.
Start
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......