![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 89](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886089.webp)
Installation and wiring
Control circuit
FR-F800
2 - 61
2.6.6
When supplying 24 V external power to the control circuit
Connect the 24 V external power supply across ter24 and SD. The 24 V external power supply
enables I/O terminal ON/OFF operation, operation panel displays, control functions, and communi-
cation during communication operation even at power-OFF of inverter's main circuit power supply.
When the main circuit power supply is turned ON, the power supply source changes from the 24 V ex-
ternal power supply to the main circuit power supply.
Specification of the applicable 24 V external power supply
For the latest information about OMRON power supply, contact OMRON corporation.
Starting and stopping the 24 V external power supply operation
●
Supplying 24 V external power while the main circuit power is OFF starts the 24 V external power
supply operation. Likewise, turning OFF the main circuit power while supplying 24 V external
power starts the 24 V external power supply operation.
●
Turning ON the main circuit power stops the 24 V external power supply operation and enables
the normal operation.
Item
Rated specification
Input voltage
23 to 25.5 V DC
Input current
1.4 A or less
Tab. 2-24:
Specification of the applicable 24 V external power supply
Model
Manufacturer
S8JX-N05024C
Specifications: Capacity 50 W, output voltage (DC) 24 V, output current 2.1 A
Installation method: Front installation with cover
or
S8VS-06024
Specifications: Capacity 60 W, output voltage (DC) 24 V, output current 2.5 A
Installation method: DIN rail installation
OMRON Corporation
Tab. 2-25:
Commercially available products (as of February 2015)
NOTES
When the 24 V external power is supplied while the main circuit power supply is OFF, the inverter
operation is disabled.
In the initial setting, when the main power supply is turned ON during the 24 V external power
supply operation, a reset is performed in the inverter, then the power supply changes to the main
circuit power supply. (The reset can be disabled using Pr. 30, refer to page 5-552.)
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......