(G) Control parameters
Parameters
5 - 540
Application for variable-torque load (Pr. 14 = "1", initial value)
●
The output voltage will change in square curve against the output frequency at the base frequen-
cy or lower. (1.75th-power curve for FR-F820-01540(37K) or higher, and FR-F840-00770(37K) or
higher.)
●
Set this parameter when driving a load with load torque change proportionally against the square
of the rotation speed, such as fan and pump.
Fig. 5-262:
Variable-torque load
I002751E
NOTE
Pr. 14 will become enabled at the time of V/F control.
Parameters referred to
Pr. 0
Torque boost
=>
Pr. 3
Base frequency
=>
Pr. 178 to Pr. 182
(input terminal function selection)
=>
100%
Output frequency (Hz)
Pr. 3 Base frequency
Ou
tp
u
t v
o
lt
a
g
e
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......