Parameters
5 - 522
5.12.8
Initial settings and specifications of Ethernet communication (FR-F800-E)
Use the following parameters to perform required settings for Ethernet communication between the
inverter and other stations.
To make communication between other devices and the inverter, perform the initial settings of the in-
verter parameters to match the communication specifications.
Pr.
Name
Initial
value
Setting range
Description
1434
Ethernet IP address 1
192
0 to 255
Enter the IP address of the inverter to be
connected to Ethernet.
1435
Ethernet IP address 2
168
0 to 255
1436
Ethernet IP address 3
50
0 to 255
1437
Ethernet IP address 4
1
0 to 255
1438
Subnet mask 1
255
0 to 255
Enter the subnet mask of the network to which
the inverter belongs.
1439
Subnet mask 2
255
0 to 255
1440
Subnet mask 3
255
0 to 255
1441
Subnet mask 4
0
0 to 255
1427
Ethernet function
selection 1
5001
502, 5000 to
5002, 5006 to
5008, 5010 to
5013, 9999,
45237, 61450
Set the application, protocol, etc.
1428
Ethernet function
selection 2
45237
502, 5000 to
5002, 5006 to
5008, 5010 to
5013, 9999,
45237, 61450
1429
Ethernet function
selection 3
9999
502, 5000 to
5002, 5006 to
5008, 5010 to
5013, 9999,
45237, 61450
1426
Link speed and duplex
mode selection
0
0 to 4
Set the communication speed and the
communication mode (full-duplex/half-duplex).
1455
N642
Keepalive time
3600 s
1 to 7200 s
When no response is returned for an alive check
message (KeepAlive ACK) for the time (s) set in
Pr. 1455 multiplied by 4 elapsed, the connection
will be forced to be closed.
1431
N643
Ethernet signal loss
detection function
selection
0
0
Signal loss detection
disabled
Set the availability of
the signal loss
detection and select
the action when
Ethernet
communication is
interrupted by physical
factors.
1
A warning (EHR) is
output for a signal loss.
2
A warning (EHR) and
the Alarm (LF) signal
are output for a signal
loss
3
A protective function
(E.EHR) is activated for a
signal loss.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......