(F) Setting of acceleration/deceleration time and acceleration/deceleration pattern
Parameters
5 - 112
Acceleration/deceleration operation
●
When the acceleration signal (RH) is turned ON, the set frequency increases. The increased speed
at this time is determined by the setting of Pr. 44 "Second acceleration/deceleration time". Turning
OFF the RH signal will stop increasing the set frequency and run the motor at the frequency at
that time.
●
When the deceleration signal (RM) is turned ON, the set frequency decreases. The decreased speed
at this time is determined by the setting of Pr. 45 "Second deceleration time". When Pr. 45 = "9999",
the deceleration speed is the same as Pr. 44 setting. Turning OFF the RM signal will stop decreasing
the set frequency and runs the motor at the frequency at that time.
●
When Pr. 59 = any of "11, 12 or 13", deceleration can be performed to a frequency equal to or lower
than the main speed (External operation mode frequency except multi-speed or PU operation
mode frequency).
I002563E
Fig. 5-26:
Example of the remote setting function
I002564E
Fig. 5-27:
Acceleration/deceleration operation
NOTE
While the RT signal is OFF, Pr. 44 "Second acceleration/deceleration time" and Pr. 45 "Second
deceleration time" are used as the set frequency accelerating/decelerating time at turn ON of the
acceleration/deceleration signal. If the Pr. 7 and Pr. 8 settings are longer, the acceleration/deceler-
ation time set by Pr. 7 and Pr. 8 are applied.
While the RT signal is ON, Pr. 44 and Pr. 45 settings are used as the acceleration/deceleration time
regardless of the Pr. 7 and Pr. 8 settings.
0
0Hz
∗1
Ou
tput fr
equen
cy
(H
Z
)
Set frequency
Acceleration (RH)
Deceleration (RM)
Clear (RL)
Forward rotation (STF)
Power supply
*1 External operation frequency (other than multi-speed) or PU running frequency
ON
When Pr. 59 = "1, 2, 11, 12"
When Pr. 59 = "1, 11"
When Pr. 59 = "3, 13"
When Pr. 59 = "2, 3, 12, 13"
Time
0 Hz
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
0
Output fr
equ
e
nc
y
(HZ)
Main speed
Minimum
frequency
Forward rotation (STF)
Acceleration (RH)
Deceleration (RM)
Pr. 59 = “1, 2, 3”
Decelerates to the main speed
Time
Decelerates to the minimum frequency
Pr. 59 = “ 11, 12, 13”
ON
ON
ON
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......