![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 265](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886265.webp)
Parameters
(E) Environment setting parameters
FR-F800
5 - 93
Life display of the main circuit capacitor (Pr. 258, Pr. 259) (Standard models)
●
The deterioration degree of the main circuit capacitor is displayed in Pr. 258.
●
With the main circuit capacitor capacity at factory shipment as 100%, the capacitor life is displayed
in Pr. 258 every time measurement is made. When the measured value falls to 85% or lower, Pr. 255
bit 1 is turned ON and also a warning is output to the Y90 signal.
●
Measure the capacitor capacity according to the following procedure and check the deterioration
degree of the capacitor capacity.
Check that the motor is connected and at a stop.
Set "1" (measuring start) in Pr. 259.
Switch the power OFF. The inverter applies DC voltage to the motor to measure the capacitor
capacity while the inverter is OFF.
After confirming that the power lamp is OFF, turn ON the power again.
!
Check that "3" (measurement complete) is set in Pr. 259, read Pr. 258, and check the deteriora-
tion degree of the main circuit capacitor.
NOTE
For accurate life measurement of the main circuit capacitor, wait three hours or longer after turn-
ing OFF. The temperature left in the main circuit capacitor affects measurement.
Pr. 259
Description
Remarks
0
No measurement
Initial value
1
Measurement start
Measurement starts when the power supply is
switched OFF
2
During measurement
Only displayed and cannot be set
3
Measurement complete
8
Forced end
9
Measurement error
Tab. 5-44:
Parameter 259
NOTES
When the main circuit capacitor life is measured under the following conditions, "forced end"
(Pr. 259 = "8") or "measurement error" (Pr. 259 = "9") may occur, or the status may remain in "meas-
urement start" (Pr. 259 = "1"). To perform measurement, first eliminate the following conditions.
Under the following conditions, even if "measurement complete" (Pr. 259 = "3") is reached, meas-
urement cannot be performed correctly.
●
FR-HC2, FR-CV, MT-RC, or a sine wave filter is connected.
●
Terminals R1/L11, S1/L21 or DC power supply is connected to terminals P/+ and N/-.
●
The power supply is switched ON during measurement.
●
The motor is not connected to the inverter.
●
The motor is running (coasting).
●
The motor capacity is smaller than the inverter capacity by two ranks or more.
●
The inverter is tripped or a fault occurred while the power was OFF.
●
The inverter output is shut off with the MRS signal.
●
The start command is given while measuring.
●
The applied motor setting is incorrect.
Operation environment: surrounding air temperature (annual average of 40 °C (free from corro-
sive gas, flammable gas, oil mist, dust and dirt)).
Output current (80% of the inverter rating)
Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent
starts and stops of the magnetic contactor must be avoided.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......