(E) Environment setting parameters
Parameters
5 - 64
Reset selection (P.E100)
When P.E100 = "1" or Pr. 75 ="1, 3, 15, 17, 100, 103, 115, or 117" is set, reset (reset command via RES sig-
nal or communication) input is enabled only when the protective function is activated.
Disconnected PU detection (P.E101)
If the PU (FR-DU08/FR-PU07) is detected to be disconnected from the inverter for 1 s or longer while
P.E101 = "1" or Pr. 75 = "2, 3, 16, 17, 102, 103, 116, or 117", PU disconnection (E.PUE) is displayed and
the inverter output is shut off.
PU stop selection (P.E102)
●
Stop can be performed by inputting
from the PU in any of the operation modes of PU
operation, External operation and network operation.
●
When stop is performed by the PU stop function, "PS" is displayed on the PU. A fault output is not
provided.
●
When P.E102 = "0" or Pr. 75 = "0 to 3, 100 to 103" is set, deceleration stop using
is valid only
in the PU operation mode.
NOTES
When the reset signal (RES) is input during operation, the motor coasts since the inverter being
reset shuts off the output. Also, the cumulative values of electronic thermal O/L relay are cleared.
The input of the PU reset key is only enabled when the protective function is activated, regardless
of the P.E100 and Pr. 75 settings.
NOTES
When the PU has been disconnected since before power-ON, the output is not shut off.
To restart, confirm that the PU is connected and then reset.
When P.E101 = "0" or Pr. 75 = "0, 1, 14, 15, 100, 101, 114, or 115" (operation continues even when
PU disconnected), decelerates to a stop when PU is disconnected during PU JOG operation.
When RS-485 communication operation is performed through the PU connector, the reset selec-
tion/PU stop selection function is valid but the disconnected PU detection function is invalid. (The
communication is checked according to Pr. 122 "PU communication check time interval".)
NOTE
When Pr. 551 "PU mode operation command source selection" = "1" (PU mode RS-485 terminal),
deceleration stop is performed even when
is input during operation in PU mode via RS-485
communication.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......