Parameters
(A) Application parameters
FR-F800
5 - 433
●
For the standard model, remove the jumpers between terminals R/L1 and R1/L11 and terminals
S/L2 and S1/L21, and connect terminals R1/L11 and P/+ and terminals S1/L21 and N/–.
●
If an undervoltage, power failure or input phase loss occurs when Pr. 261 "Power failure stop
selection"
≠
"0", the motor decelerates to a stop.
●
The power failure time deceleration stop function operates as follows at an input phase loss.
●
For the separated converter type, remove the jumpers between terminals R/L1 and R1/L11 and
terminals S/L2 and S1/L21 of the converter unit, and connect terminals R1/L11 and P/+ and
terminals S1/L21 and N/–. Do not remove the jumpers of terminal R1/L11 and terminal S1/L21 of
the inverter. (In the initial status of the separated converter type, terminals P/+ and R1/L11 and
terminals N/- and S1/L21 are connected.)
●
For the separated converter type, connect the terminal to which PWF signal of the converter unit
is assigned and the terminal to which X48 signal of the inverter is assigned. Also, set Pr. 261 of the
converter unit in accordance with the inverter setting. (Refer to the Instruction Manual of the
converter unit.)
I002875E_G
Fig. 5-213:
Connection of the separated converter type inverter
Pr. 261
Pr. 872
Operation when an input phase loss occurs
0
0
Continuous operation
1
Input phase loss (E.ILT)
1, 2
0
Continuous operation
1
Deceleration stop
21, 22
—
Deceleration stop
Tab. 5-210:
Operation at input phase loss depending on Pr. 261 and Pr. 872
R/L1
S/L2
T/L3
R1/L11
S1/L21
U
V
W
M
R1/L11
S1/L21
P/+
N/-
P/+
N/-
RDA
MRS(X10)
RSO
RES
PWF
X48
SE
PC
Connect terminals
R1/L11 and P/+ and
terminals S1/L21 and
N/–.
Power supply
Remove the jumper
Inverter
Converter unit
Keep the jumpers of terminal R1/L11
and terminal S1/L21 connected.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......