![Mitsubishi Electric FR-F820-00046 Instruction Manual Download Page 257](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886257.webp)
Parameters
(E) Environment setting parameters
FR-F800
5 - 85
Rated frequency (Pr. 999 = "20 (50 Hz), 21 (60 Hz)")
5.4.16
Extended parameter display and user group function
This function restricts the parameters that are read by the operation panel and the parameter unit.
The read value is always "9999".
Pr.
Name
Initial value
Pr. 999 = "21"
Pr. 999 = "20"
Refer to
page
FM type
CA type
3
Base frequency
60 Hz
50 Hz
60 Hz
50 Hz
4
Multi-speed setting (high speed)
60 Hz
50 Hz
60 Hz
50 Hz
20
Acceleration/deceleration
reference frequency
60 Hz
50 Hz
60 Hz
50 Hz
37
Speed display
0
0
55
Frequency monitoring reference
60 Hz
50 Hz
60 Hz
50 Hz
66
Stall prevention operation
reduction starting frequency
60 Hz
50 Hz
60 Hz
50 Hz
125 (903)
Terminal 2 frequency setting gain
frequency
60 Hz
50 Hz
60 Hz
50 Hz
126 (905)
Terminal 4 frequency setting gain
frequency
60 Hz
50 Hz
60 Hz
50 Hz
263
Subtraction starting frequency
60 Hz
50 Hz
60 Hz
50 Hz
266
Power failure deceleration time
switchover frequency
60 Hz
50 Hz
60 Hz
50 Hz
386
Frequency for maximum input
pulse
60 Hz
50 Hz
60 Hz
50 Hz
390
% setting reference frequency
60 Hz
50 Hz
60 Hz
50 Hz
505
Speed setting reference
60 Hz
50 Hz
60 Hz
50 Hz
584
Auxiliary motor 1 starting
frequency
60 Hz
50 Hz
60 Hz
50 Hz
585
Auxiliary motor 2 starting
frequency
60 Hz
50 Hz
60 Hz
50 Hz
586
Auxiliary motor 3 starting
frequency
60 Hz
50 Hz
60 Hz
50 Hz
C14 (918)
Terminal 1 gain frequency (speed)
60 Hz
50 Hz
60 Hz
50 Hz
1013
Running speed after emergency
drive retry reset
60 Hz
50 Hz
60 Hz
50 Hz
Tab. 5-38:
Influence of Pr. 999 on the rated frequencies
Pr.
Name
Initial value
Setting range
Description
FM
CA
160
E440
User group read selection
9999
0
9999
Only simple mode parameters can be
displayed.
0
Simple mode and extended
parameters can be displayed.
1
Only parameters registered in user
groups can be displayed.
172
E441
User group registered display/
batch clear
0
(0 to 16)
Displays the number of groups that
are registered as user groups.
(Read-only)
9999
Batch clear of user group registrations
173
E442
User group registration
9999
0 to 1999, 9999
Sets the parameter number to register
for the user group.
174
E443
User group clear
9999
0 to 1999, 9999
Sets the parameter number to clear
from the user group.
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......