Parameters
(G) Control parameters
FR-F800
5 - 537
5.13.2
Base frequency, voltage
Use this function to adjust the inverter outputs (voltage, frequency) to match with the motor rating.
Setting of base frequency (Pr. 3)
●
When operating a standard motor, generally set the rated frequency of the motor in Pr. 3 "Base
frequency". When the motor operation require switching to the commercial power supply, set the
power supply frequency in Pr. 3.
●
When the frequency on the motor rating plate is only "50 Hz", make sure to set to "50 Hz". When
it is set to "60 Hz", the voltage will drop too much, causing insufficient torque. As a result, the
inverter may trip due to overload.
A caution is required especially in case of Pr. 14 "Load pattern selection" = "1" (variable torque
load).
●
When using the Mitsubishi constant torque motor, set Pr. 3 to 60 Hz.
Setting multiple base frequencies (Pr. 47)
●
To change the base frequency when using single inverter switching between multiple motors,
use Pr. 47 "Second V/F (base frequency)".
●
Pr. 47 will become enabled when the RT signal turns ON.
Pr.
Name
Initial value
Setting
range
Description
FM
CA
3
G001
Base frequency
60 Hz
50 Hz
0 to 590 Hz
Set the frequency at the rated motor torque.
(50 Hz/60 Hz)
19
G002
Base frequency voltage
9999
8888
0 to 1000 V
Set the base voltage.
8888
95% of the power supply voltage
9999
Same as the power supply voltage
47
G011
Second V/F
(base frequency)
9999
0 to 590 Hz
Set the base frequency at the RT signal ON.
9999
Second V/F disabled
Fig. 5-260:
Output voltage related to the output frequency
I002749E
NOTES
The RT signal acts as the second function selection signal and makes the other second functions
valid. (Refer to page 5-291.)
The RT signal is assigned to the terminal RT in the initial status. It is also possible to assign the RT
signal to other terminal by setting "3" on Pr. 178 to Pr. 189 (input terminal function selection).
V/F
V/F
V/F
Ou
tp
ut
vol
tag
e
(V
)
Output frequency
(Hz)
Pr. 3
Pr. 47
Pr. 19
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......