Protective functions
Check first when you have a trouble
FR-F800
6 - 35
Parameter
setting
Start signal operation selection is set by Pr. 250
"Stop selection".
Check the Pr. 250 setting and the connection of
STF and STR signals.
The motor has decelerated to a stop when
power failure deceleration stop function is
selected.
When power is restored, ensure the safety, and
turn OFF the start signal once, then turn ON
again to restart.
When Pr. 261 "Power failure stop selection" = "2
or 12", the motor automatically restarts after
the power is restored.
Performing auto tuning.
When offline auto tuning ends, press STOP/
RESET key of the operation panel for the PU
operation. For the External operation, turn OFF
the start signal (STF or STR).
This operation resets the offline auto tuning,
and the PU's monitor display returns to the
normal indication.
(Without this operation, next operation cannot
be started.)
The automatic restart after instantaneous
power failure function or power failure stop
function has been activated.
(Performing overload operation during input
phase loss may cause voltage insufficiency, and
that may result in detection of power failure.)
Set Pr. 872 "Input phase loss protection
selection" ="1" (input phase failure protection
active).
Disable the automatic restart after
instantaneous power failure function and
power failure stop function.
Reduce the load.
Increase the acceleration time if the function
was activated during acceleration.
The motor test operation is selected under PM
motor control.
Check the Pr. 800 "Control method selection"
setting.
When the FR-HC2, FR-CV, or FR-CC2 is used, the
input logic setting of the X10 signal is incorrect.
Set Pr. 599 = "0" (initial value for standard
models) to use the X10 signal with the NO
contact input specification, and Pr. 599 = "1"
(initial value for separated converter types) to
use the X10 signal with the NC contact input
specification.
Load
Load is too heavy.
Reduce the load.
⎯
Shaft is locked.
Inspect the machine (motor).
⎯
Check
points
Possible cause
Countermeasure
Refer to
page
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......