Offline auto tuning
The offline auto tuning enables the optimal operation of an motor.
What is offline auto tuning?
Under Advanced magnetic flux vector control operation, measuring motor constants automatically
(offline auto tuning) enables optimal operation of motors even when motor constants vary, when a
motor of another company is used or when the wiring distance is long.
For the offline auto tuning for a PM motor, refer to page 5-316.
Pr.
Name
Initial
value
Setting range
Description
684
C000
Tuning data unit
switchover
0
0
Internal data converted value
1
The value is indicated with "A, Ω, mH or %".
71
C100
Applied motor
0
0 to 6, 13 to 16, 20, 23, 24, 40,
43, 44, 50, 53, 54, 70, 73, 74,
210, 213, 214, 240, 243, 244,
8090, 8093, 8094, 9090, 9093,
9094
By selecting a motor, the thermal
characteristic and motor constant of each
motor are set.
80
C101
Motor capacity
9999
0.4 to 55 kW
Set the applied motor capacity.
9999
V/F control
81
C102
Number of motor
poles
9999
2, 4, 6, 8, 10, 12
Set the number of motor poles.
9999
V/F control
9
C103
Electronic thermal
O/L relay
Inverter
rated
current
0 to 500 A
Set the rated motor current.
83
C104
Rated motor voltage
200/
400 V
0 to 1000 V
Set the rated motor voltage (V).
84
C105
Rated motor
frequency
9999
10 to 400 Hz
Set the rated motor frequency (Hz).
9999
Use the value set in Pr. 3 "Base frequency".
707
C107
Motor inertia
(integer)
9999
10 to 999, 9999
Set the motor inertia.
9999: Uses the constant value of Mitsubishi
motor (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-
HRCA and so on).
724
C108
Motor inertia
(exponent)
9999
0 to 7, 9999
96
C110
Auto tuning setting/
status
0
0
No offline auto tuning
1
Performs offline auto tuning without
rotating the motor
11
Performs offline auto tuning without
rotating the motor (V/f control, IPM motor
MM-EFS/MM-THE4))
(Refer to page 5-316)
101
Performs offline auto tuning by rotating the
motor
Magnetic flux
Magnetic flux
Magnetic flux
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......