Parameters
(H) Protective function parameter
FR-F800
5 - 163
5.7.6
I/O phase loss protection selection
The output phase loss protection function, which stops the inverter output if one of the three phases
(U, V, W) on the inverter's output side (load side) is lost, can be disabled.
The input phase loss protective function on the inverter input side (R/L1, S/L2, T/L3) can be enabled.
The setting is available only for standard models.
Output phase loss protection selection (Pr. 251)
●
When Pr. 251 = "0", output phase loss (E.LF) protection is disabled.
Input phase loss protection selection (Pr. 872) (Standard models)
When Pr. 872 = "1", input phase loss (E.ILF) protection will be activated if one of three phases is de-
tected to be lost for 1 s continuously.
Pr.
Name
Initial
value
Setting
range
Description
251
H200
Output phase loss
protection selection
1
0
Without output phase loss protection
1
With output phase loss protection
872
H201
Input phase loss
protection selection
0
0
Without input phase loss protection
1
With input phase loss protection
NOTES
When several motors are connected, output phase loss cannot be detected even if the wiring to
one motor loses phase.
If an input phase is lost while Pr. 872 = "1" (with input phase loss protection), Pr. 261 "Power failure
stop selection" ≠ "0" (power failure stop function enabled), the motor decelerates to stop without
outputting E.ILF.
In the case of R/L1, S/L2 phase loss, the input phase loss protection will not operate, and the
inverter will trip.
If an input phase loss continues for a long time, the converter section and capacitor lives of the
inverter will be shorter.
Parameters referred to
Pr. 261
Power failure stop selection
=>
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......