Parameters
(H) Protective function parameter
FR-F800
5 - 185
Setting multiple stall prevention operation levels (Pr. 48, Pr. 49)
●
By setting Pr. 49 "Second stall prevention operation frequency" = "9999" and turning ON the RT
signal, Pr. 48 "Second stall prevention operation level" will be enabled.
●
For Pr. 48, set the stall prevention operation level that is effective in the output frequency range
between 0 Hz and Pr. 49. However, the operation level is Pr. 22 during acceleration.
●
Stop-on-contact operation can be used by decreasing the Pr. 48 setting and loosening the
reduction torque (torque when stopped).
For the stall prevention operation level, the smaller of Pr. 22 and Pr. 48 has precedence.
When Pr. 858 = "4 (analog input to terminal 4 for stall prevention operation level)" or Pr. 868 = "4
(analog input to terminal 1 for stall prevention operation level)", turning ON the RT signal will not
enable the second stall prevention function. (Input to the terminal 4 or terminal 1 is valid.)
Pr. 49 setting
Operation
0 (initial value)
The second stall prevention function disabled.
0.01 Hz to 590 Hz
The second stall prevention function operates according to the frequency.
The second stall prevention function operates according to the RT signal.
RT signal ON: stall level Pr. 48
RT signal OFF: stall level Pr. 22
Tab. 5-81:
Settings of parameter 49
I002599E
Fig. 5-68:
Stall prevention operation level setting example
NOTES
When Pr. 49 ≠ "9999" (level change according to frequency) and Pr. 48 = "0%", the stall prevention
function will be disabled at or lower than the frequency set in Pr. 49.
The RT signal is assigned to the terminal RT in the initial status. Set "3" in any of Pr. 178 to Pr. 189
(input terminal function selection) to assign the RT signal to another terminal.
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
The RT signal acts as the second function selection signal and makes the other second functions
valid. (Refer to page 5-291.)
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Output
frequency (Hz)
Output
frequency
During acceleration
During deceleration/constant speed
Running frequency
Pr. 49
Set frequency is
Pr. 49 or less
Pr. 48 used
Time
Stall
prevention
level
Pr. 22 used
Pr. 48
Stall pr
evention
oper
a
tion curr
en
t
Pr. 49
Set frequency
Output
frequency (Hz)
Output
frequency
Time
Stall
prevention
level
Set frequency
exceeds Pr. 49
Pr. 48 used
Pr. 22 used
Set frequency
Pr. 49
Summary of Contents for FR-F820-00046
Page 2: ......
Page 4: ......
Page 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Page 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Page 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Page 900: ...Outline dimension drawings Specifications 8 26 ...
Page 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Page 930: ...EC Declarations of Conformity Appendix A 30 ...
Page 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Page 932: ...EC Declarations of Conformity Appendix A 32 ...
Page 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Page 934: ...EC Declarations of Conformity Appendix A 34 ...
Page 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Page 936: ...EC Declarations of Conformity Appendix A 36 ...
Page 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Page 938: ...EC Declarations of Conformity Appendix A 38 ...
Page 939: ......